Worked example
Example: 400 A, 6,000 h, copper 8,000/mm²·km. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Load current (rms, per conductor) | 400.00 A |
| Equivalent full-load (loss-load) hours per year, Σ I²t / I² | 6,000.0 h |
| Energy cost per kWh | 8.0000 - |
| Conductor cost per mm² per km (variable part) | 8,000.0 - |
| Annual capital charge rate | 12.000 % |
| Resistivity at operating temperature | 2.1000e-08 Ω·m |
| Conductors per circuit | 3.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Economic cross-section | 409.88 mm² |
| Annual loss cost per km at A_econ | 1,180,449 |
| Annual capital charge per km at A_econ | 1,180,449 |
| Economic current density | 0.97590 A/mm² |
Open this example in the calculator and change any input.
Formula
\(A_{econ} = I\sqrt{\frac{\rho\,t_a\,c_e}{c_c\,r}}\ \text{(per conductor, consistent units)}, \quad C_{loss} = C_{cap}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I\) | Load current (rms, per conductor) | A |
| \(t_a\) | Equivalent full-load (loss-load) hours per year, Σ I²t / I² | s |
| \(c_e\) | Energy cost per kWh | - |
| \(c_c\) | Conductor cost per mm² per km (variable part) | - |
| \(r\) | Annual capital charge rate | - |
| \(\rho\) | Resistivity at operating temperature | Ω·m |
| \(n\) | Conductors per circuit | - |
| \(A_{econ}\) | Economic cross-section | m² |
| \(C_{loss}\) | Annual loss cost per km at A_econ | - |
| \(C_{cap}\) | Annual capital charge per km at A_econ | - |
| \(J\) | Economic current density | A/m² |
Method and standards
Kelvin's law.
Where it is used
- Long, heavily loaded feeders and busducts.
- Energy-efficiency cable sizing.
Common mistakes
- Using peak instead of loss-equivalent hours.
- Including fixed (installation) costs that do not scale with area.
Assumptions and limits
- Cost linear in area. t_a is the loss-load (I²-weighted) equivalent hours, Σ I²t / I² for the I entered, not the operating hours.
- Energy cost per kWh and conductor cost per mm² per km are converted to SI inside (per J and per m³ of conductor).
References
- Kelvin's law for economic conductor size (annual loss cost = annual capital charge on the area-dependent cost)
Questions and answers
Why choose a larger conductor than thermal rating needs?
Losses go as 1/A; on heavily used circuits the saving in losses over the years exceeds the extra copper or aluminium.
What current density results?
Typically 0.5–1.5 A/mm² for copper with high utilisation, far below thermal limits.
What do the defaults represent?
A 400 A three-core circuit used 6,000 h/year at 8 per kWh, copper at 8,000 per mm²·km and a 12 % capital charge.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.