Conductor Resistance at Operating Temperature

Resistance of a copper or aluminium conductor at its operating temperature from the value at a reference temperature and the temperature coefficient, with I²R losses.

Thermal power plantProcess steam and utilitiesElectric motorElectrician and wireman licence examinations

Inputs

Examples: Copper 0.1 Ω at 20 °C to 90 °C, 100 AAluminium 0.25 Ω at 20 °C to 70 °C, 60 ACopper winding 1.2 Ω at 25 °C to 115 °C, 15 A

From the conductor maker's data; copper is about 0.0039 per K and aluminium about 0.0040 per K at 20 °C.

Results

DC resistance; AC skin and proximity effects add to it in large conductors.

Resistance at the operating temperature0.30038Ω
Resistance ratio1.2015
I²R loss at the reference temperature0.90000kW
I²R loss at the operating temperature1.0813kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Copper 0.1 Ω at 20 °C to 90 °C, 100 A. The inputs, in the units selected above:

InputValue
Resistance at the reference temperature0.10000 Ω
Reference temperature20.000 °C
Operating temperature90.000 °C
Temperature coefficient of resistance at T₁ (per K)0.003930 -
Current (for the loss)100.00 A

Applying the formula below gives:

ResultValue
Resistance at the operating temperature0.12751 Ω
Resistance ratio1.2751
I²R loss at the reference temperature1.0000 kW
I²R loss at the operating temperature1.2751 kW

Open this example in the calculator and change any input.

Formula

\(R_2 = R_1 [1 + \alpha_1 (T_2 - T_1)]\)

\(P = I^2 R\)

Variables

Symbol Meaning SI unit
\(R_1\) resistance at the reference temperature Ω
\(T_1\) reference temperature K
\(T_2\) operating temperature K
\(\alpha_1\) temperature coefficient at T₁ 1/K
\(I\) current A
\(R_2\) resistance at the operating temperature Ω
\(R_2 / R_1\) resistance ratio -
\(P_1\) I²R loss at T₁ W
\(P_2\) I²R loss at T₂ W
\(P\) I²R loss W

Method and standards

Metal resistance rises almost linearly with temperature; the coefficient α applies at the reference temperature T₁. The conductor maker gives α for the conductor material.

Where it is used

  • Correcting cable resistance for voltage-drop and loss calculations at operating temperature.
  • Correcting winding resistance tests.
  • Estimating losses in hot busbars.

Common mistakes

  • Using α at 20 °C with a different reference temperature.
  • Mixing per-km and total resistances.
  • Ignoring AC resistance in large cables.

Assumptions and limits

  • Linear relation; fine over the normal operating range.
  • DC resistance.
  • α is the coefficient at the reference temperature T₁; a 20 °C value used with another T₁ is flagged (α₁ = α₂₀/[1 + α₂₀(T₁ − 20 °C)]).

References

  • R₂ = R₁ [1 + α (T₂ − T₁)]

Questions and answers

How much does copper resistance rise from 20 °C to 90 °C?

About 27.5 % with α = 0.00393 per K: 0.1 Ω becomes 0.1275 Ω, and the I²R loss at 100 A rises from 1.0 to 1.28 kW.

Why correct winding resistance readings?

Motor and transformer winding resistances are measured cold and must be corrected to the reference temperature before comparing with test values.

Does this include AC effects?

No. It is DC resistance; skin and proximity effects add to the AC resistance of large conductors.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.