Cable Tray Fill Calculator

Fill of a cable tray from the number and diameter of cables and the tray width and depth, against an allowed fill, with the most cables that fit.

Thermal power plantProcess steam and utilities

Inputs

Examples: 40 cables of 18 mm in 300 x 75 mm, 40 %12 cables of 42 mm in 600 x 100 mm, 40 %100 cables of 9 mm in 150 x 50 mm, 50 %

Your project specification or wiring code sets this.

Results

The fill is above the allowed value.

Total cross-section of the cables63.617cm²
Cross-section of the tray75.000cm²
Fill84.823%
Most cables within the allowed fill58.000
Smallest tray width for these cables at the allowed fill254.47mm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 40 cables of 18 mm in 300 x 75 mm, 40 %. The inputs, in the units selected above:

InputValue
Number of cables40.000 -
Overall diameter of each cable18.000 mm
Tray width (inside)300.00 mm
Usable depth of the tray75.000 mm
Allowed fill40.000 %

Applying the formula below gives:

ResultValue
Total cross-section of the cables101.79 cm²
Cross-section of the tray225.00 cm²
Fill45.239 %
Most cables within the allowed fill35.000
Smallest tray width for these cables at the allowed fill339.29 mm

Open this example in the calculator and change any input.

Formula

\(f = \frac{n\, \pi d^2 / 4}{W H}, \quad n_{max} = \left\lfloor \frac{f_{max}\, W H}{\pi d^2/4} \right\rfloor\)

Variables

Symbol Meaning SI unit
\(n\) Number of cables -
\(d\) Overall diameter of each cable m
\(W\) Tray width (inside) m
\(H\) Usable depth of the tray m
\(f_{max}\) Allowed fill -
\(A_c\) Total cross-section of the cables m²
\(A_t\) Cross-section of the tray m²
\(f\) Fill -
\(n_{max}\) Most cables within the allowed fill -
\(W_{min}\) Smallest tray width for these cables at the allowed fill m

Method and standards

Area ratio.

Where it is used

  • Tray and trunking selection.
  • Checking spare capacity.

Common mistakes

  • Ignoring grouping derating.
  • No space for future cables.

Assumptions and limits

  • Cables of one size.
  • A pure area ratio: it ignores how round cables pack and the single-layer or diameter-sum rules that wiring codes apply to large power cables, so n_max may not be attainable in practice.

References

  • Geometric fill ratio (sum of cable cross-sections / tray cross-section)

Questions and answers

What is the fill of 40 cables of 18 mm in a 300 × 75 mm tray?

45 %.

How many fit at 40 %?
Does fill affect current rating?

Yes: grouped cables are derated; power cables are often laid in a single layer instead.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.