Worked example
Example: 40 cables of 18 mm in 300 x 75 mm, 40 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Number of cables | 40.000 - |
| Overall diameter of each cable | 18.000 mm |
| Tray width (inside) | 300.00 mm |
| Usable depth of the tray | 75.000 mm |
| Allowed fill | 40.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total cross-section of the cables | 101.79 cm² |
| Cross-section of the tray | 225.00 cm² |
| Fill | 45.239 % |
| Most cables within the allowed fill | 35.000 |
| Smallest tray width for these cables at the allowed fill | 339.29 mm |
Open this example in the calculator and change any input.
Formula
\(f = \frac{n\, \pi d^2 / 4}{W H}, \quad n_{max} = \left\lfloor \frac{f_{max}\, W H}{\pi d^2/4} \right\rfloor\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | Number of cables | - |
| \(d\) | Overall diameter of each cable | m |
| \(W\) | Tray width (inside) | m |
| \(H\) | Usable depth of the tray | m |
| \(f_{max}\) | Allowed fill | - |
| \(A_c\) | Total cross-section of the cables | m² |
| \(A_t\) | Cross-section of the tray | m² |
| \(f\) | Fill | - |
| \(n_{max}\) | Most cables within the allowed fill | - |
| \(W_{min}\) | Smallest tray width for these cables at the allowed fill | m |
Method and standards
Area ratio.
Where it is used
- Tray and trunking selection.
- Checking spare capacity.
Common mistakes
- Ignoring grouping derating.
- No space for future cables.
Assumptions and limits
- Cables of one size.
- A pure area ratio: it ignores how round cables pack and the single-layer or diameter-sum rules that wiring codes apply to large power cables, so n_max may not be attainable in practice.
References
- Geometric fill ratio (sum of cable cross-sections / tray cross-section)
Questions and answers
What is the fill of 40 cables of 18 mm in a 300 × 75 mm tray?
45 %.
How many fit at 40 %?
Does fill affect current rating?
Yes: grouped cables are derated; power cables are often laid in a single layer instead.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.