Worked example
Example: 2 000 A at 1.2 A/mm², two 10 mm bars. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Current per phase | 2,000.0 A |
| Current density | 1.2000 A/mm² |
| Bar thickness | 10.000 mm |
| Bars per phase | 2.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Cross-section needed per phase | 1,666.7 mm² |
| Width of each bar | 83.333 mm |
Open this example in the calculator and change any input.
Formula
\(A = \frac{I}{J}, \quad w = \frac{A}{n\, t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I\) | Current per phase | A |
| \(J\) | Current density | A/m² |
| \(t\) | Bar thickness | m |
| \(n\) | Bars per phase | - |
| \(A\) | Cross-section needed per phase | m² |
| \(w\) | Width of each bar | m |
Method and standards
Current density method.
Where it is used
- Panel and bus duct first sizing.
- Checking existing bars.
Common mistakes
- Using an open-air density inside a sealed panel.
- Ignoring short-circuit forces.
Assumptions and limits
- Uniform current density, shared equally by the bars. In AC service several bars per phase share unevenly (proximity and skin effect); more than two bars per phase are flagged.
References
- A = I / J (current density method)
Questions and answers
What busbar for 2000 A at 1.2 A/mm² with two 10 mm bars?
1667 mm², so two bars 83 mm wide: use the next standard width.
What current density should I use?
It depends on metal, ventilation and allowed rise; take it from your panel standard or the bar maker.
Is that enough?
No: check temperature rise by test or the maker's tables, and the fault withstand.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.