FireCADCalc

AWG to mm² Wire Size Converter

Diameter and cross-section in mm² of an American Wire Gauge (AWG) size by the defining formula, with the resistance per km for copper or another metal.

Thermal power plantProcess steam and utilities

Inputs

Examples: 10 AWG copper4/0 AWG aluminium24 AWG copper

Default: annealed copper (IACS). Aluminium is about 0.0283 Ω·mm²/m.

Results

Solid round wire. Stranded conductors of the same AWG have the same metal area but a larger overall diameter.

Diameter11.684mm
Cross-section107.22mm²
Resistance per unit length at 20 °C0.26361Ω/km

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 AWG copper. The inputs, in the units selected above:

InputValue
AWG number (0 = 1/0, −1 = 2/0, −2 = 3/0, −3 = 4/0)10.000 -
Resistivity of the conductor at 20 °C0.017241 Ω·mm²/m

Applying the formula below gives:

ResultValue
Diameter2.5882 mm
Cross-section5.2612 mm²
Resistance per unit length at 20 °C3.2771 Ω/km

Open this example in the calculator and change any input.

Formula

\(d\,[\text{in}] = 0.005 \times 92^{(36 - n)/39}, \quad A = \frac{\pi d^2}{4}, \quad r = \frac{\rho}{A}\)

Variables

Symbol Meaning SI unit
\(n\) AWG number (0 = 1/0, −1 = 2/0, −2 = 3/0, −3 = 4/0) -
\(\rho\) Resistivity of the conductor at 20 °C Ω·m
\(d\) Diameter m
\(A\) Cross-section m²
\(r\) Resistance per unit length at 20 °C Ω/m

Method and standards

The AWG series is a geometric progression between 36 AWG and 4/0.

Where it is used

  • Reading US drawings and equipment manuals.
  • Instrument and control wiring.

Common mistakes

  • Confusing AWG with SWG.
  • Treating 1/0 as AWG 1.

Assumptions and limits

  • Solid wire dimensions; whole-number gauges only.

References

  • ASTM B258 (AWG diameters: 0.005 in × 92^((36 − n)/39))
  • IEC 60028 (resistivity of annealed copper)

Questions and answers

What is 10 AWG in mm²?

5.26 mm², diameter 2.588 mm.

How do sizes step?

Every 3 gauge numbers doubles the area; every 6 doubles the diameter.

Which metric cable replaces it?

The next larger standard mm² size, checked for current rating.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.