Worked example
Example: 10 AWG copper. The inputs, in the units selected above:
| Input | Value |
|---|---|
| AWG number (0 = 1/0, −1 = 2/0, −2 = 3/0, −3 = 4/0) | 10.000 - |
| Resistivity of the conductor at 20 °C | 0.017241 Ω·mm²/m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Diameter | 2.5882 mm |
| Cross-section | 5.2612 mm² |
| Resistance per unit length at 20 °C | 3.2771 Ω/km |
Open this example in the calculator and change any input.
Formula
\(d\,[\text{in}] = 0.005 \times 92^{(36 - n)/39}, \quad A = \frac{\pi d^2}{4}, \quad r = \frac{\rho}{A}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | AWG number (0 = 1/0, −1 = 2/0, −2 = 3/0, −3 = 4/0) | - |
| \(\rho\) | Resistivity of the conductor at 20 °C | Ω·m |
| \(d\) | Diameter | m |
| \(A\) | Cross-section | m² |
| \(r\) | Resistance per unit length at 20 °C | Ω/m |
Method and standards
The AWG series is a geometric progression between 36 AWG and 4/0.
Where it is used
- Reading US drawings and equipment manuals.
- Instrument and control wiring.
Common mistakes
- Confusing AWG with SWG.
- Treating 1/0 as AWG 1.
Assumptions and limits
- Solid wire dimensions; whole-number gauges only.
References
- ASTM B258 (AWG diameters: 0.005 in × 92^((36 − n)/39))
- IEC 60028 (resistivity of annealed copper)
Questions and answers
What is 10 AWG in mm²?
5.26 mm², diameter 2.588 mm.
How do sizes step?
Every 3 gauge numbers doubles the area; every 6 doubles the diameter.
Which metric cable replaces it?
The next larger standard mm² size, checked for current rating.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.