FireCADCalc

UPS Efficiency: Losses, Cooling and Yearly Cost

Power lost in a UPS at a load and efficiency, the extra cooling energy to remove it, and the yearly cost, compared between two UPS efficiencies.

Inputs

Examples: Illustrative 60 kW data roomLight load, old UPSNo cooling credit

Accepted: 0.1 to 100,000 kW
Accepted: 50 to 100 %
Accepted: 50 to 100 %
Accepted: 0 to 10
Accepted: 0 to 8,760 h
Accepted: 0 to 1,000

Results

A UPS that delivers P at efficiency η draws P/η, losing P(1/η − 1) as heat in the UPS room; air conditioning then spends that heat divided by its COP to remove it. Efficiency depends strongly on load: double-conversion UPSs are least efficient at light load, which is where many run with redundancy. Use efficiencies at the real load, and eco or line-interactive modes where the application allows.

Loss of UPS 13.5294kW
Loss of UPS 21.0526kW
Yearly energy (loss plus cooling), UPS 143.285MWh
Yearly energy (loss plus cooling), UPS 212.909MWh
Cost saved per year with UPS 2243,002

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 60 kW data room. The inputs, in the units selected above:

InputValue
IT or critical load60.000 kW
Efficiency of UPS 1 at this load92.000 %
Efficiency of UPS 2 at this load96.000 %
Cooling system COP (0 = no cooling)3.0000 -
Hours per year8,760.0 h
Electricity price per kWh8.0000 -

Applying the formula below gives:

ResultValue
Loss of UPS 15.2174 kW
Loss of UPS 22.5000 kW
Yearly energy (loss plus cooling), UPS 160.939 MWh
Yearly energy (loss plus cooling), UPS 229.200 MWh
Cost saved per year with UPS 2253,913

Open this example in the calculator and change any input.

Formula

\(P_L = P\left(\frac1\eta - 1\right), \quad E = P_L\left(1 + \frac1{COP}\right)t\)

Variables

Symbol Meaning SI unit
\(P\) IT or critical load W
\(\eta_1\) Efficiency of UPS 1 at this load -
\(\eta_2\) Efficiency of UPS 2 at this load -
\(COP\) Cooling system COP (0 = no cooling) -
\(t\) Hours per year s
\(c\) Electricity price per kWh -
\(P_{L1}\) Loss of UPS 1 W
\(P_{L2}\) Loss of UPS 2 W
\(E_1\) Yearly energy (loss plus cooling), UPS 1 J
\(E_2\) Yearly energy (loss plus cooling), UPS 2 J
\(\Delta C\) Cost saved per year with UPS 2 -

Method and standards

UPS losses.

Where it is used

  • Data centres and control rooms.
  • UPS replacement decisions.

Common mistakes

  • Using full-load efficiency for a lightly loaded UPS.
  • Ignoring the cooling energy.

Assumptions and limits

  • Constant load and efficiency.

References

  • UPS loss and cooling energy balance

Questions and answers

How much does a 4-point better UPS save on 60 kW?

About 2.7 kW of loss and 0.9 kW of cooling: about 32 MWh a year running continuously.

Why include cooling?

Every kW of UPS loss is heat the air conditioning must remove, adding about a third more energy at COP 3.

What do the defaults represent?

An illustrative 60 kW load on a 92 % UPS against a 96 % one, running all year with cooling at COP 3 and 8 per kWh.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.