FireCADCalc

Lead-Acid Battery State of Charge from Open-Circuit Voltage

Electrolyte specific gravity and state of charge of a flooded lead-acid battery from its rested open-circuit voltage, by the OCV–specific gravity relation.

Inputs

Examples: Illustrative 12 V battery at 12.5 V24 V bank at 24.4 VTropical acid 2 V cell at 2.05 V

Accepted: 1.5 to 1,000 V
Accepted: 1 to 500
Accepted: 0.8 to 0.9
Accepted: 1.15 to 1.35
Accepted: 1 to 1.2

Results

The rested cell voltage of a lead-acid cell follows its acid strength: V_oc ≈ SG + 0.84 to 0.85 V. State of charge is roughly linear in specific gravity between the discharged and charged values for the design. Let the battery rest several hours (ideally 24) after charging or discharging; surface charge makes the voltage read high. Sealed AGM and gel cells use different acid strengths, so use the maker's OCV table where available.

Cell open-circuit voltage2.0500V
Estimated specific gravity1.2050
State of charge84.000%
Battery voltage when full2.0700V

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 12 V battery at 12.5 V. The inputs, in the units selected above:

InputValue
Battery open-circuit voltage (rested)12.500 V
Cells in series6.0000 -
OCV minus specific gravity constant0.84500 -
Specific gravity fully charged1.2650 -
Specific gravity fully discharged1.1200 -

Applying the formula below gives:

ResultValue
Cell open-circuit voltage2.0833 V
Estimated specific gravity1.2383
State of charge81.609 %
Battery voltage when full12.660 V

Open this example in the calculator and change any input.

Formula

\(SG = \frac{V_{oc}}{n} - k, \quad SOC = \frac{SG - SG_{empty}}{SG_{full} - SG_{empty}}\)

Variables

Symbol Meaning SI unit
\(V_{oc}\) Battery open-circuit voltage (rested) V
\(n\) Cells in series -
\(k\) OCV minus specific gravity constant -
\(SG_{full}\) Specific gravity fully charged -
\(SG_{empty}\) Specific gravity fully discharged -
\(V_{cell}\) Cell open-circuit voltage V
\(SG\) Estimated specific gravity -
\(SOC\) State of charge -
\(V_{full}\) Battery voltage when full V

Method and standards

State of charge.

Where it is used

  • Battery maintenance and storage checks.
  • Off-grid and UPS battery monitoring.

Common mistakes

  • Measuring right after charging.
  • Using flooded-cell values for AGM or gel.

Assumptions and limits

  • Rested battery; uniform acid; linear SG–SOC.

References

  • Open-circuit voltage and acid specific gravity relation

Questions and answers

Why must the battery rest before measuring?

Charging leaves a surface charge that raises the voltage for hours; discharging depresses it.

Is OCV accurate for SOC?

Within about 10 % for a rested, healthy flooded battery; hydrometer readings of each cell are better.

What do the defaults represent?

An illustrative 12 V six-cell flooded battery resting at 12.5 V, with 1.265 full and 1.12 empty specific gravity.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Linden and Reddy, Handbook of Batteries, 4th ed. (McGraw-Hill, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.