Worked example
Example: Illustrative 12 V battery at 12.5 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Battery open-circuit voltage (rested) | 12.500 V |
| Cells in series | 6.0000 - |
| OCV minus specific gravity constant | 0.84500 - |
| Specific gravity fully charged | 1.2650 - |
| Specific gravity fully discharged | 1.1200 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Cell open-circuit voltage | 2.0833 V |
| Estimated specific gravity | 1.2383 |
| State of charge | 81.609 % |
| Battery voltage when full | 12.660 V |
Open this example in the calculator and change any input.
Formula
\(SG = \frac{V_{oc}}{n} - k, \quad SOC = \frac{SG - SG_{empty}}{SG_{full} - SG_{empty}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_{oc}\) | Battery open-circuit voltage (rested) | V |
| \(n\) | Cells in series | - |
| \(k\) | OCV minus specific gravity constant | - |
| \(SG_{full}\) | Specific gravity fully charged | - |
| \(SG_{empty}\) | Specific gravity fully discharged | - |
| \(V_{cell}\) | Cell open-circuit voltage | V |
| \(SG\) | Estimated specific gravity | - |
| \(SOC\) | State of charge | - |
| \(V_{full}\) | Battery voltage when full | V |
Method and standards
State of charge.
Where it is used
- Battery maintenance and storage checks.
- Off-grid and UPS battery monitoring.
Common mistakes
- Measuring right after charging.
- Using flooded-cell values for AGM or gel.
Assumptions and limits
- Rested battery; uniform acid; linear SG–SOC.
References
- Open-circuit voltage and acid specific gravity relation
Questions and answers
Why must the battery rest before measuring?
Charging leaves a surface charge that raises the voltage for hours; discharging depresses it.
Is OCV accurate for SOC?
Within about 10 % for a rested, healthy flooded battery; hydrometer readings of each cell are better.
What do the defaults represent?
An illustrative 12 V six-cell flooded battery resting at 12.5 V, with 1.265 full and 1.12 empty specific gravity.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Linden and Reddy, Handbook of Batteries, 4th ed. (McGraw-Hill, 2011)