FireCADCalc

Battery State of Charge by Coulomb Counting

Battery state of charge after charging or discharging at a constant current for a time, with coulombic efficiency, and the time to reach empty or full.

Thermal power plant

Inputs

Examples: Illustrative 100 Ah, 80 %, 20 A for 2 hCharging 50 A for 1 h from 30 %UPS 7 Ah, 5 A for 30 min

Accepted: 0.00027778 to 277,780 Ah
Accepted: 0 to 100 %
Accepted: -100,000 to 100,000 A
Accepted: 0 to 2,777.8 h
Accepted: 50 to 100 %

Results

SOC = SOC₀ − ∫ I dt / C with charge current scaled by the coulombic efficiency. Counting drifts with current-sensor offset; real battery management systems correct it with voltage at rest.

State of charge after t64.286%
Charge moved2.5000Ah
Time to empty (discharge) or full (charge)1.4000h
C-rate0.71429

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 100 Ah, 80 %, 20 A for 2 h. The inputs, in the units selected above:

InputValue
Battery capacity100.00 Ah
Initial state of charge80.000 %
Current (positive discharge, negative charge)20.000 A
Time2.0000 h
Coulombic efficiency on charge99.000 %

Applying the formula below gives:

ResultValue
State of charge after t40.000 %
Charge moved40.000 Ah
Time to empty (discharge) or full (charge)4.0000 h
C-rate0.20000

Open this example in the calculator and change any input.

Formula

\(SOC(t) = SOC_0 - \frac{1}{C}\int_0^t I\,dt\)

Variables

Symbol Meaning SI unit
\(C\) Battery capacity C
\(SOC_0\) Initial state of charge -
\(I\) Current (positive discharge, negative charge) A
\(t\) Time s
\(\eta_c\) Coulombic efficiency on charge -
\(SOC\) State of charge after t -
\(\Delta Q\) Charge moved C
\(t_{limit}\) Time to empty (discharge) or full (charge) s
\(I/C\) C-rate -

Method and standards

Coulomb counting.

Where it is used

  • Battery monitoring and UPS runtime checks.
  • Teaching battery management.

Common mistakes

  • Mixing Ah and As.
  • Ignoring charge efficiency.

Assumptions and limits

  • Constant current; capacity independent of rate.

References

  • Coulomb counting

Questions and answers

Why does coulomb counting drift?

A small sensor offset integrates over hours into a large SOC error, so management systems recalibrate at full charge or from rest voltage.

Does capacity depend on current?

Yes for lead-acid (Peukert effect); lithium-ion is much less sensitive, which makes coulomb counting work well.

What do the defaults represent?

An illustrative 100 Ah battery at 80 % discharged at 20 A for two hours.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.