Worked example
Example: Illustrative LFP 250/kWh, 6000 cycles. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Battery pack cost (per kWh of capacity) | 250.00 - |
| Cycle life to end of life | 6,000.0 - |
| Depth of discharge per cycle | 90.000 % |
| Average capacity over life (fraction of new) | 90.000 % |
| Round-trip efficiency | 90.000 % |
| Charging energy price (per kWh) | 0.050000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Lifetime energy delivered per kWh of capacity (kWh) | 4,860.0 |
| Wear cost per kWh delivered | 0.051440 |
| Charging cost per kWh delivered | 0.055556 |
| Total cost per kWh delivered | 0.10700 |
Open this example in the calculator and change any input.
Formula
\(c_w = \frac{C_b}{N\cdot DoD\cdot f_{avg}}, \quad c = c_w + \frac{c_{ch}}{\eta}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_b\) | Battery pack cost (per kWh of capacity) | - |
| \(N\) | Cycle life to end of life | - |
| \(DoD\) | Depth of discharge per cycle | - |
| \(f_{avg}\) | Average capacity over life (fraction of new) | - |
| \(\eta\) | Round-trip efficiency | - |
| \(c_{ch}\) | Charging energy price (per kWh) | - |
| \(E_{life}\) | Lifetime energy delivered per kWh of capacity (kWh) | - |
| \(c_w\) | Wear cost per kWh delivered | - |
| \(c_{ch}/\eta\) | Charging cost per kWh delivered | - |
| \(c\) | Total cost per kWh delivered | - |
Method and standards
Battery throughput cost.
Where it is used
- Battery arbitrage and peak shaving cases.
- EV and home battery economics.
Common mistakes
- Using nameplate cycle life at a different DoD.
- Ignoring capacity fade over life.
Assumptions and limits
- Cycle ageing only; constant prices.
References
- Battery throughput cost
Questions and answers
Why does wear cost matter for arbitrage?
Every cycle uses up part of the battery; arbitrage pays only if the price spread exceeds wear cost plus the efficiency loss.
How do LFP and NMC compare?
LFP cells typically last 4,000–8,000 cycles, NMC 1,500–3,000, so LFP has much lower wear cost per kWh for daily cycling.
What do the defaults represent?
An illustrative 250 per kWh pack lasting 6,000 cycles at 90 % depth of discharge, averaging 90 % of new capacity, 90 % round trip and charging at 0.05 per kWh.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9