FireCADCalc

Battery Capacity Correction for Low Temperature and Ageing

Capacity available at a low temperature by a linear temperature coefficient, and the rated capacity to buy for a load with temperature, ageing and design margins.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 200 Ah at 5 COutdoor cabinet at -10 CWarm room 25 C, ageing only

Accepted: 1 to 277,780 Ah
Accepted: -40.15 to 49.85 °C
Accepted: 9.85 to 39.85 °C
Accepted: 0 to 0.02 1/K
Accepted: 1 to 1.5
Accepted: 1 to 1.5

Results

Available capacity C_T = C_r[1 + λ(T − T_r)] (about 0.6 % per kelvin for lead-acid at long discharge rates, more at high rates). Rated capacity C_r = C_L·k_a·k_d/k_T: ageing factor 1.25 lets the battery reach 80 % capacity before it is replaced. Use the maker's temperature curves where available.

Temperature capacity factor100.00%
Rated capacity required625.00Ah
Overall sizing factor1.2500

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 200 Ah at 5 C. The inputs, in the units selected above:

InputValue
Capacity the load needs (at the rated discharge rate)200.00 Ah
Lowest electrolyte temperature5.0000 °C
Rating temperature25.000 °C
Capacity temperature coefficient0.006000 1/K
Ageing factor1.2500 -
Design margin1.1000 -

Applying the formula below gives:

ResultValue
Temperature capacity factor88.000 %
Rated capacity required312.50 Ah
Overall sizing factor1.5625

Open this example in the calculator and change any input.

Formula

\(k_T = 1 + \lambda(T - T_r), \quad C_r = \frac{C_Lk_ak_d}{k_T}\)

Variables

Symbol Meaning SI unit
\(C_L\) Capacity the load needs (at the rated discharge rate) C
\(T\) Lowest electrolyte temperature K
\(T_r\) Rating temperature K
\(\lambda\) Capacity temperature coefficient 1/K
\(k_a\) Ageing factor -
\(k_d\) Design margin -
\(k_T\) Temperature capacity factor -
\(C_r\) Rated capacity required C
\(C_r/C_L\) Overall sizing factor -

Method and standards

Capacity correction.

Where it is used

  • Substation and UPS battery sizing.
  • Outdoor telecom and solar battery banks.

Common mistakes

  • Applying the high-temperature side as a credit.
  • Using ambient instead of electrolyte temperature.

Assumptions and limits

  • Linear coefficient over the range; rating rate matches the duty.

References

  • Linear capacity–temperature relation with sizing margins

Questions and answers

Why does a cold battery deliver less?

Electrolyte diffusion and reaction rates slow, raising resistance and cutting usable capacity.

Why add an ageing factor?

Capacity fades over life; sizing for 125 % lets the battery still meet the load when it has faded to 80 %.

What do the defaults represent?

An illustrative load needing 200 Ah, battery at 5 °C rated at 25 °C, λ = 0.006/K, ageing 1.25 and design margin 1.1.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Linden and Reddy, Handbook of Batteries, 4th ed. (McGraw-Hill, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.