Worked example
Example: Illustrative 200 Ah at 5 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Capacity the load needs (at the rated discharge rate) | 200.00 Ah |
| Lowest electrolyte temperature | 5.0000 °C |
| Rating temperature | 25.000 °C |
| Capacity temperature coefficient | 0.006000 1/K |
| Ageing factor | 1.2500 - |
| Design margin | 1.1000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Temperature capacity factor | 88.000 % |
| Rated capacity required | 312.50 Ah |
| Overall sizing factor | 1.5625 |
Open this example in the calculator and change any input.
Formula
\(k_T = 1 + \lambda(T - T_r), \quad C_r = \frac{C_Lk_ak_d}{k_T}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_L\) | Capacity the load needs (at the rated discharge rate) | C |
| \(T\) | Lowest electrolyte temperature | K |
| \(T_r\) | Rating temperature | K |
| \(\lambda\) | Capacity temperature coefficient | 1/K |
| \(k_a\) | Ageing factor | - |
| \(k_d\) | Design margin | - |
| \(k_T\) | Temperature capacity factor | - |
| \(C_r\) | Rated capacity required | C |
| \(C_r/C_L\) | Overall sizing factor | - |
Method and standards
Capacity correction.
Where it is used
- Substation and UPS battery sizing.
- Outdoor telecom and solar battery banks.
Common mistakes
- Applying the high-temperature side as a credit.
- Using ambient instead of electrolyte temperature.
Assumptions and limits
- Linear coefficient over the range; rating rate matches the duty.
References
- Linear capacity–temperature relation with sizing margins
Questions and answers
Why does a cold battery deliver less?
Electrolyte diffusion and reaction rates slow, raising resistance and cutting usable capacity.
Why add an ageing factor?
Capacity fades over life; sizing for 125 % lets the battery still meet the load when it has faded to 80 %.
What do the defaults represent?
An illustrative load needing 200 Ah, battery at 5 °C rated at 25 °C, λ = 0.006/K, ageing 1.25 and design margin 1.1.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Linden and Reddy, Handbook of Batteries, 4th ed. (McGraw-Hill, 2011)