Plant Load Factor, Availability, Auxiliary Power and Heat Rate

Plant load factor, availability factor, auxiliary power share, net generation, gross and net heat rate and specific fuel consumption of a power plant over a period.

Thermal power plantSugar mill and cogenerationChemical and fertiliserPulp and paperBoilerSteam turbine

Inputs

Examples: 30 MW for a year: 200 GWh, 18 GWh auxiliary, 180 000 t of 15 MJ/kg coal12 MW captive, one month: 7 200 MWh, 650 MWh aux, 9 000 t bagasse 8 MJ/kg500 MW unit, quarter: 900 GWh, 52 GWh aux, 540 000 t of 16.5 MJ/kg

Results

Plant load factor82.192%
Availability factor93.607%
Auxiliary power, share of gross generation5.7778%
Net generation848,000MWh
Gross heat rate9,900.0kJ/kWh
Net heat rate10,507kJ/kWh
Gross efficiency36.364%
Net efficiency34.263%
Specific fuel consumption (gross)0.60000kg/kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 30 MW for a year: 200 GWh, 18 GWh auxiliary, 180 000 t of 15 MJ/kg coal. The inputs, in the units selected above:

InputValue
Rated (installed) capacity30.000 MW
Length of the period8,760.0 h
Hours the unit was available to run8,300.0 h
Gross generation in the period200,000 MWh
Auxiliary consumption in the period18,000 MWh
Fuel burnt in the period180,000 t
Gross calorific value of the fuel15,000 kJ/kg

Applying the formula below gives:

ResultValue
Plant load factor76.104 %
Availability factor94.749 %
Auxiliary power, share of gross generation9.0000 %
Net generation182,000 MWh
Gross heat rate13,500 kJ/kWh
Net heat rate14,835 kJ/kWh
Gross efficiency26.667 %
Net efficiency24.267 %
Specific fuel consumption (gross)0.90000 kg/kWh

Open this example in the calculator and change any input.

Formula

\(PLF = \frac{E_g}{P_r\, t_p}, \quad PAF = \frac{t_a}{t_p}, \quad APC = \frac{E_{aux}}{E_g}\)

\(HR_g = \frac{m_F\, GCV}{E_g}, \quad HR_n = \frac{m_F\, GCV}{E_g - E_{aux}}, \quad SFC = \frac{m_F}{E_g}\)

Variables

Symbol Meaning SI unit
\(P_r\) Rated (installed) capacity W
\(t_p\) Length of the period s
\(t_a\) Hours the unit was available to run s
\(E_g\) Gross generation in the period J
\(E_{aux}\) Auxiliary consumption in the period J
\(m_F\) Fuel burnt in the period kg
\(GCV\) Gross calorific value of the fuel J/kg
\(PLF\) Plant load factor -
\(PAF\) Availability factor -
\(APC\) Auxiliary power, share of gross generation -
\(E_n\) Net generation J
\(HR_g\) Gross heat rate J/J
\(HR_n\) Net heat rate J/J
\(\eta_g\) Gross efficiency -
\(\eta_n\) Net efficiency -
\(SFC\) Specific fuel consumption (gross) kg/J

Method and standards

The standard performance definitions: plant load factor on rated capacity, availability on time, auxiliary consumption on gross generation, heat rate on gross calorific value of the fuel. Efficiency is the inverse of heat rate.

Where it is used

  • Monthly and yearly plant performance reports.
  • Comparing units or plants on a common basis.
  • Checking coal consumption against generation.

Common mistakes

  • Using declared capacity instead of rated capacity for PLF (that gives a different factor).
  • Mixing GCV as received with fuel weighed on another basis.
  • Forgetting that auxiliary power on shutdown days still counts.

Assumptions and limits

  • One unit or a plant treated as one unit.
  • Fuel weighed and analysed on the same basis.

References

  • Central Electricity Authority (India)
  • Review of Performance of Thermal Power Stations: definitions of PLF
  • availability and auxiliary consumption

Questions and answers

What is the PLF of a 30 MW plant that generated 200 GWh in a year?

200 GWh over 30 MW × 8 760 h = 76.1 %. With 18 GWh auxiliary consumption the net generation is 182 GWh.

What is the difference between PLF and availability?

PLF is energy generated over what the rated capacity could give; availability is the time the unit was ready to run. A unit can be available but backed down, giving high availability and low PLF.

How is the heat rate found?

Fuel heat over generation: 180 000 t of 15 MJ/kg coal for 200 GWh is 3.75 kJ per kJ (13 500 kJ/kWh) gross, 4.12 net.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.