Worked example
Example: 30 MW for a year: 200 GWh, 18 GWh auxiliary, 180 000 t of 15 MJ/kg coal. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated (installed) capacity | 30.000 MW |
| Length of the period | 8,760.0 h |
| Hours the unit was available to run | 8,300.0 h |
| Gross generation in the period | 200,000 MWh |
| Auxiliary consumption in the period | 18,000 MWh |
| Fuel burnt in the period | 180,000 t |
| Gross calorific value of the fuel | 15,000 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Plant load factor | 76.104 % |
| Availability factor | 94.749 % |
| Auxiliary power, share of gross generation | 9.0000 % |
| Net generation | 182,000 MWh |
| Gross heat rate | 13,500 kJ/kWh |
| Net heat rate | 14,835 kJ/kWh |
| Gross efficiency | 26.667 % |
| Net efficiency | 24.267 % |
| Specific fuel consumption (gross) | 0.90000 kg/kWh |
Open this example in the calculator and change any input.
Formula
\(PLF = \frac{E_g}{P_r\, t_p}, \quad PAF = \frac{t_a}{t_p}, \quad APC = \frac{E_{aux}}{E_g}\)
\(HR_g = \frac{m_F\, GCV}{E_g}, \quad HR_n = \frac{m_F\, GCV}{E_g - E_{aux}}, \quad SFC = \frac{m_F}{E_g}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_r\) | Rated (installed) capacity | W |
| \(t_p\) | Length of the period | s |
| \(t_a\) | Hours the unit was available to run | s |
| \(E_g\) | Gross generation in the period | J |
| \(E_{aux}\) | Auxiliary consumption in the period | J |
| \(m_F\) | Fuel burnt in the period | kg |
| \(GCV\) | Gross calorific value of the fuel | J/kg |
| \(PLF\) | Plant load factor | - |
| \(PAF\) | Availability factor | - |
| \(APC\) | Auxiliary power, share of gross generation | - |
| \(E_n\) | Net generation | J |
| \(HR_g\) | Gross heat rate | J/J |
| \(HR_n\) | Net heat rate | J/J |
| \(\eta_g\) | Gross efficiency | - |
| \(\eta_n\) | Net efficiency | - |
| \(SFC\) | Specific fuel consumption (gross) | kg/J |
Method and standards
The standard performance definitions: plant load factor on rated capacity, availability on time, auxiliary consumption on gross generation, heat rate on gross calorific value of the fuel. Efficiency is the inverse of heat rate.
Where it is used
- Monthly and yearly plant performance reports.
- Comparing units or plants on a common basis.
- Checking coal consumption against generation.
Common mistakes
- Using declared capacity instead of rated capacity for PLF (that gives a different factor).
- Mixing GCV as received with fuel weighed on another basis.
- Forgetting that auxiliary power on shutdown days still counts.
Assumptions and limits
- One unit or a plant treated as one unit.
- Fuel weighed and analysed on the same basis.
References
- Central Electricity Authority (India)
- Review of Performance of Thermal Power Stations: definitions of PLF
- availability and auxiliary consumption
Questions and answers
What is the PLF of a 30 MW plant that generated 200 GWh in a year?
200 GWh over 30 MW × 8 760 h = 76.1 %. With 18 GWh auxiliary consumption the net generation is 182 GWh.
What is the difference between PLF and availability?
PLF is energy generated over what the rated capacity could give; availability is the time the unit was ready to run. A unit can be available but backed down, giving high availability and low PLF.
How is the heat rate found?
Fuel heat over generation: 180 000 t of 15 MJ/kg coal for 200 GWh is 3.75 kJ per kJ (13 500 kJ/kWh) gross, 4.12 net.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.