Worked example
Example: 30 MW coal unit, 20 t/h at 18.6 MJ/kg, auxiliaries 9 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat input from | Fuel flow and GCV |
| Gross generator output | 30.000 MW |
| Auxiliary power consumption | 2.7000 MW |
| Fuel flow | 20,000 kg/h |
| Gross calorific value of the fuel | 18,600 kJ/kg |
| Gross efficiency | 30.000 % |
| Gross heat rate | 12,000 kJ/kWh |
Applying the formula below gives:
| Result | Value |
|---|---|
| Gross heat rate | 12,400 kJ/kWh |
| Net heat rate | 13,626 kJ/kWh |
| Gross efficiency | 29.032 % |
| Net efficiency | 26.419 % |
| Heat input from fuel (on GCV) | 103.33 MW |
| Net output | 27.300 MW |
| Auxiliary consumption | 9.0000 % |
| Fuel flow | 20,000 kg/h |
| Specific fuel consumption (gross) | 0.66667 kg/kWh |
Open this example in the calculator and change any input.
Formula
\(\dot Q_{in} = \dot m_f\,GCV \quad\text{or}\quad \dot Q_{in} = \frac{P_g}{\eta_{g,in}} \quad\text{or}\quad \dot Q_{in} = HR_{g,in}\,P_g\)
\(HR_g = \frac{\dot Q_{in}}{P_g} \qquad HR_n = \frac{\dot Q_{in}}{P_n} \qquad \eta_g = \frac{1}{HR_g} \qquad \eta_n = \frac{1}{HR_n} \qquad P_n = P_g - P_{aux}\)
\(\dot m_{f,out} = \frac{\dot Q_{in}}{GCV} \qquad SFC = \frac{\dot m_{f,out}}{P_g}\)
A heat rate in J/J times 3 600 is kJ/kWh; times 859.85 it is kcal/kWh.
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{basis}\) | heat input from fuel flow, efficiency or heat rate | – |
| \(P_g\) | gross generator output | W |
| \(P_{aux}\) | auxiliary power consumption | W |
| \(\dot m_f\) | fuel flow, entered | kg/s |
| \(GCV\) | gross calorific value of the fuel | J/kg |
| \(\eta_{g,in}\) | gross efficiency, entered | – |
| \(HR_{g,in}\) | gross heat rate, entered | J/J |
| \(HR_g\) | gross heat rate | J/J |
| \(HR_n\) | net heat rate | J/J |
| \(\eta_g\) | gross efficiency | – |
| \(\eta_n\) | net efficiency | – |
| \(\dot Q_{in}\) | heat input from fuel, on GCV | W |
| \(P_n\) | net output | W |
| \(P_{aux}/P_g\) | auxiliary consumption as a share of gross output | – |
| \(\dot m_{f,out}\) | fuel flow | kg/s |
| \(SFC\) | specific fuel consumption, gross | kg/J |
Method and standards
Definitions of heat rate and thermal efficiency as used in ASME PTC 46 and in the station heat rate reporting of India's Central Electricity Authority: heat input on the gross calorific value divided by electrical output. Unit factors from NIST SP 811 (1 kWh = 3.6 MJ, 1 kcal_IT = 4.1868 kJ, 1 Btu_IT = 1.055 056 kJ).
Where it is used
- Monthly performance reports of power and captive plants.
- Comparing units, fuels and seasons on fuel per kWh.
- Regulatory and tariff filings that use station heat rate.
Common mistakes
- Mixing gross and net output.
- Using GCV in one place and NCV in another.
- Quoting turbine heat rate as plant heat rate: divide by boiler efficiency first.
Assumptions and limits
- Heat input on GCV. European figures are often on NCV and are 4–10 % lower in heat rate; do not mix the two.
- Steady load over the period; for a period average use the energy generated and the fuel burnt in the period.
- Heat in fuel only; heat credits from process steam export (cogeneration) are not deducted.
References
- ASME PTC 46 (terms)
- CEA India (station heat rate reporting)
- NIST SP 811 (unit factors)
Questions and answers
What is heat rate?
Heat put in as fuel per unit of electricity produced. 1 kWh is 3 600 kJ, so a plant at 36 % efficiency has a heat rate of 3 600/0.36 = 10 000 kJ/kWh (2 388 kcal/kWh).
What is the difference between gross and net heat rate?
Gross heat rate uses the generator output; net heat rate uses the output after the plant's own auxiliary consumption. With 8.5 % auxiliaries a gross heat rate of 2 250 kcal/kWh is a net heat rate of 2 459 kcal/kWh.
What is specific coal consumption?
Fuel burnt per kWh generated. A 30 MW unit burning 20 t/h of coal uses 0.667 kg/kWh.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.