Tidal Range Power: Energy per Tide and Annual Output of a Basin

Theoretical and net energy from a single tidal basin per tide, the annual energy and average power from basin area, tidal range and efficiency.

Thermal power plant

Inputs

Examples: La Rance-like: 22 km2, 8.5 m range, 33 %, 706 tides, 240 MWLagoon 11.5 km2, 7 m, 30 %, 706 tides, 320 MWGulf of Kutch-type 170 km2, 5 m, 25 %, 706 tides, 900 MW

Accepted: 0.01 to 10,000 km²
Accepted: 0.5 to 20 m
Accepted: 5 to 100 %
Accepted: 1 to 1,500
Accepted: 990 to 1,040 kg/m³
Accepted: 0.001 to 10,000 MW

Results

E = ½ρgAR² is the potential energy of a basin full to the range above low water; ebb generation, turbine head limits and the time needed to fill and empty mean only about a third is recovered.

Theoretical energy per tide2,219.1MWh
Net energy per tide732.30MWh
Annual energy517.00GWh
Average power58.978MW
Capacity factor24.574%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: La Rance-like: 22 km2, 8.5 m range, 33 %, 706 tides, 240 MW. The inputs, in the units selected above:

InputValue
Basin area22.000 km²
Tidal range8.5000 m
Overall conversion efficiency33.000 %
Tides used per year (semidiurnal: about 706)706.00 -
Seawater density1,025.0 kg/m³
Installed capacity240.00 MW

Applying the formula below gives:

ResultValue
Theoretical energy per tide2,219.1 MWh
Net energy per tide732.30 MWh
Annual energy517.00 GWh
Average power58.978 MW
Capacity factor24.574 %

Open this example in the calculator and change any input.

Formula

\(E_{tide} = \frac{1}{2}\rho gAR^2, \quad E_{yr} = \eta n_tE_{tide}\)

Variables

Symbol Meaning SI unit
\(A\) Basin area m²
\(R\) Tidal range m
\(\eta\) Overall conversion efficiency -
\(n_t\) Tides used per year (semidiurnal: about 706) -
\(\rho\) Seawater density kg/m³
\(P_{inst}\) Installed capacity W
\(E_{tide}\) Theoretical energy per tide J
\(E_{net}\) Net energy per tide J
\(E_{yr}\) Annual energy J
\(\bar P\) Average power W
\(CF\) Capacity factor -

Method and standards

Potential energy of a tidal basin.

Where it is used

  • Screening tidal barrage and lagoon sites.
  • Teaching and exam calculations on tidal power.

Common mistakes

  • Using the spring range for the whole year.
  • Forgetting the conversion efficiency.

Assumptions and limits

  • Single basin, mean range; theoretical potential energy.

Questions and answers

Why is the energy proportional to the square of the range?

Both the water volume and its average height above low water grow with the range.

What overall efficiency is realistic?

About 25–35 % of the theoretical energy for single-basin ebb generation; two-way generation and pumping add a little.

What do the defaults represent?

An illustrative case: La Rance-like: 22 km2, 8.5 m range, 33 %, 706 tides, 240 MW. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Nag, Power Plant Engineering, 3rd ed. (Tata McGraw-Hill, 2008), ch. 13 (tidal power)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.