Worked example
Example: 500 km2, 1,200 mm, runoff 0.6, 80 % used, 80 m, 85 %, 80 MW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Catchment area | 500.00 km² |
| Mean annual rainfall | 1,200.0 mm |
| Runoff coefficient (share reaching the river) | 60.000 % |
| Share of the runoff used by the plant | 80.000 % |
| Net head | 80.000 m |
| Overall efficiency | 85.000 % |
| Installed capacity | 80.000 MW |
| Water density | 1,000.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Annual runoff | 3.6000e+08 m³ |
| Mean flow used | 9.1262 m³/s |
| Mean power | 6.0858 MW |
| Annual energy | 53.348 GWh |
| Capacity factor | 7.6073 % |
Open this example in the calculator and change any input.
Formula
\(V = ARC, \quad \bar Q = \frac{Vf_u}{t_{yr}}, \quad \bar P = \rho g\bar QH\eta_o, \quad E = \bar Pt_{yr}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A\) | Catchment area | m² |
| \(R\) | Mean annual rainfall | m |
| \(C\) | Runoff coefficient (share reaching the river) | - |
| \(f_u\) | Share of the runoff used by the plant | - |
| \(H\) | Net head | m |
| \(\eta_o\) | Overall efficiency | - |
| \(P_{inst}\) | Installed capacity | W |
| \(\rho\) | Water density | kg/m³ |
| \(V\) | Annual runoff | m³ |
| \(\bar Q\) | Mean flow used | m³/s |
| \(\bar P\) | Mean power | W |
| \(E\) | Annual energy | J |
| \(CF\) | Capacity factor | - |
Method and standards
Annual water balance of a catchment.
Where it is used
- Pre-feasibility screening of hydro sites.
- Checking claimed annual generation.
Common mistakes
- Mixing catchment area in km² with rainfall in mm without converting.
- Assuming all runoff can be used.
Assumptions and limits
- Annual averages; no evaporation from reservoirs beyond the runoff coefficient.
Questions and answers
What runoff coefficient should I use?
From gauged flows if they exist; otherwise 0.2–0.4 for flat cultivated land, 0.5–0.7 for hilly or forested catchments and up to 0.9 for rocky or urban ones.
Why is the capacity factor low for run-of-river plants?
Monsoon floods exceed the turbine capacity and dry-season flows fall well below it, so much of the runoff is either spilled or produces part-load output.
What do the defaults represent?
A 500 km² catchment with 1,200 mm rain, 60 % runoff and 80 % used, 80 m head, 85 % efficiency and 80 MW installed: about 9.1 m³/s, 6.1 MW mean and 53 GWh a year (capacity factor 7.6 %).
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.