Barometric Column Height and Diameter (Hugot)

Height of a barometric tail pipe as static head, velocity head and margin (Hugot eqns 40.19–40.20) and its diameter for the flow (40.22).

Sugar mill and cogenerationIAPWS-IF97 (water and steam)Condenser and cooling tower

Inputs

Examples: 770 mmHg, 3 cmHg abs, 1 m/sFast column

Hugot: 1 m/s in older designs; Webre 2–3 m/s.
Hugot's table: straight pipe of 50 mm 6.1, 100 mm 2.6, 200 mm 1.2, 400 mm 0.6, 800 mm 0.4.

Results

Hugot's example: H₀ 10.20 m, velocity head 0.10 m and 0.5 m margin give 10.80 m. The well should hold at least 1.5 times the column volume.

The water is at or above its boiling point at the condenser pressure: it would flash at the top of the column. Check the water temperature and the vacuum.

Water density988.05kg/m³
Static column for the vacuum9.9069m
Velocity head with losses0.57359m
Column height10.980m
Column diameter342.65mm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 770 mmHg, 3 cmHg abs, 1 m/s. The inputs, in the units selected above:

InputValue
Barometric pressure770.00 mmHg
Condenser pressure (absolute)3.0000 cmHg
Water temperature in the column45.000 °C
Vapour condensed11,000 kg/h
Water per kg vapour50.000 -
Velocity in the column1.0000 m/s
Loss coefficient of the column1.0000 -
Margin0.50000 m

Applying the formula below gives:

ResultValue
Water density990.22 kg/m³
Static column for the vacuum10.160 m
Velocity head with losses0.10197 m
Column height10.762 m
Column diameter447.63 mm

Open this example in the calculator and change any input.

Formula

\(H_0 = \frac{p_a - p}{\rho_w g}, \quad h = (1 + \alpha)\frac{V^2}{2g}, \quad H = H_0 + h + s, \quad D = \sqrt{\frac{4Q(W + 1)}{\rho_w\pi V}}\)

Variables

Symbol Meaning SI unit
\(p_a\) Barometric pressure Pa
\(p\) Condenser pressure (absolute) Pa
\(t_w\) Water temperature in the column K
\(Q\) Vapour condensed kg/s
\(W\) Water per kg vapour -
\(V\) Velocity in the column m/s
\(\alpha\) Loss coefficient of the column -
\(s\) Margin m
\(\rho_w\) Water density kg/m³
\(H_0\) Static column for the vacuum m
\(h\) Velocity head with losses m
\(H\) Column height m
\(D\) Column diameter m

Method and standards

Hugot's column balance.

Where it is used

  • Condenser installation.
  • Checking flooding of condensers.

Common mistakes

  • Using cold-water density.
  • Leaving out the condensate in the flow.

Assumptions and limits

  • Steady flow; sealed well.
  • The water must be below its boiling point at the condenser pressure; a note appears if not.

References

  • Hugot
  • Handbook of Cane Sugar Engineering
  • 3rd ed. (Elsevier, 1986)
  • ch. 40
  • barometric column
  • eqns 40.19–40.23
  • pp. 881–883
  • Water density from IAPWS-IF97

Questions and answers

Why add the velocity head?

Water must flow down the column, so it needs head beyond the static balance, plus losses at entry and along the pipe.

Why warm-water density?

The column holds the warm discharge water, lighter than cold water, so it must be a little taller.

How big a margin?

Hugot: about 0.5 m for surges and barometer changes.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.