Fan Compressibility Factor and Air Power

Compressibility factor relating isentropic to incompressible fan work for a pressure rise and inlet pressure, with air power and outlet-to-inlet volume ratio.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 10 kPa rise, 20 m3/sLow pressure 2.5 kPaBlower 50 kPa

Accepted: 10 to 1,000 kPa
Accepted: 0.10197 to 50,986 mmWC
Accepted: 1.1 to 1.67
Accepted: 3.6 to 36,000,000 m³/h

Results

K_p = [κ/(κ − 1)][(1 + x)^((κ−1)/κ) − 1]/x with x = Δp/p₁: the ratio of isentropic to incompressible work. It matters above a few kPa (K_p ≈ 0.98 at 10 kPa) and is used in fan testing standards in a polytropic form.

Compressibility factor0.99131
Air power Q₁ΔpK_p123.91kW
Incompressible air power125.00kW
Outlet-to-inlet volume ratio (isentropic)0.98274

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 10 kPa rise, 20 m3/s. The inputs, in the units selected above:

InputValue
Inlet pressure (absolute)101.33 kPa
Fan total pressure rise1,019.7 mmWC
Isentropic exponent1.4000 -
Inlet volume flow72,000 m³/h

Applying the formula below gives:

ResultValue
Compressibility factor0.96662
Air power Q₁ΔpK_p193.32 kW
Incompressible air power200.00 kW
Outlet-to-inlet volume ratio (isentropic)0.93498

Open this example in the calculator and change any input.

Formula

\(K_p = \frac{\kappa}{\kappa - 1}\frac{(1 + x)^{(\kappa - 1)/\kappa} - 1}{x}, \quad x = \frac{\Delta p}{p_1}\)

Variables

Symbol Meaning SI unit
\(p_1\) Inlet pressure (absolute) Pa
\(\Delta p\) Fan total pressure rise Pa
\(\kappa\) Isentropic exponent -
\(Q_1\) Inlet volume flow m³/s
\(K_p\) Compressibility factor -
\(P_u\) Air power Q₁ΔpK_p W
\(Q_1\Delta p\) Incompressible air power W
\(Q_2/Q_1\) Outlet-to-inlet volume ratio (isentropic) -

Method and standards

Fan compressibility.

Where it is used

  • High-pressure fan and blower sizing.
  • Fan test reduction.

Common mistakes

  • Using outlet volume flow with inlet-based K_p.
  • Applying it to very small pressure rises where it is 1.

Assumptions and limits

  • Ideal gas; isentropic reference.

References

  • Isentropic work ratio for fans

Questions and answers

When must compressibility be considered?

Above about 2.5 kPa pressure rise (2–3 % density change); for ID fans and blowers the error can reach several per cent.

Why is K_p below 1?

Air is compressed as it passes, so its volume shrinks and less work is needed than incompressible flow at inlet volume would suggest.

What do the defaults represent?

An illustrative 20 m³/s fan with a 10 kPa rise at atmospheric inlet pressure.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Bleier, Fan Handbook: Selection, Application and Design (McGraw-Hill, 1998)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.