Axial Fan Velocity Triangles and Blade Angles

Axial velocity, blade speed, required swirl and the inlet and outlet relative flow angles at the mean radius of an axial fan, with the de Haller ratio.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 1.2 m, hub 0.5 m, 15 m3/s, 600 PaCooling tower fan 9 m, 120 rpmMine fan 3 m, 2000 Pa

Accepted: 0.1 to 20 m
Accepted: 0.02 to 10 m
Accepted: 9.5493 to 9,549.3 rpm
Accepted: 3.6 to 36,000,000 m³/h
Accepted: 0.10197 to 1,019.7 mmWC
Accepted: 0.1 to 5 kg/m³
Accepted: 40 to 100 %

Results

Euler: Δp_t = η_hρuΔc_u at the root-mean-square radius, no inlet swirl. β measured from the plane of rotation; the blade turns the flow from β₁ to β₂. A de Haller ratio below about 0.7 means too much diffusion: separation and stall.

Axial velocity9.8244m/s
Blade speed at mean radius40.778m/s
Swirl added4.7980m/s
Inlet relative flow angle (from the plane of rotation)13.546°
Outlet relative flow angle15.272°
de Haller ratio (keep above about 0.7)0.88920

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 1.2 m, hub 0.5 m, 15 m3/s, 600 Pa. The inputs, in the units selected above:

InputValue
Tip diameter1.2000 m
Hub diameter0.50000 m
Speed1,480.0 rpm
Volume flow54,000 m³/h
Total pressure rise61.183 mmWC
Gas density1.2000 kg/m³
Hydraulic efficiency85.000 %

Applying the formula below gives:

ResultValue
Axial velocity16.049 m/s
Blade speed at mean radius71.234 m/s
Swirl added8.2578 m/s
Inlet relative flow angle (from the plane of rotation)12.697 °
Outlet relative flow angle14.297 °
de Haller ratio (keep above about 0.7)0.89002

Open this example in the calculator and change any input.

Formula

\(\Delta p_t = \eta_h\rho u\Delta c_u, \quad \tan\beta_1 = \frac{c_a}{u}, \quad \tan\beta_2 = \frac{c_a}{u - \Delta c_u}\)

Variables

Symbol Meaning SI unit
\(D_t\) Tip diameter m
\(D_h\) Hub diameter m
\(n\) Speed rad/s
\(Q\) Volume flow m³/s
\(\Delta p_t\) Total pressure rise Pa
\(\rho\) Gas density kg/m³
\(\eta_h\) Hydraulic efficiency -
\(c_a\) Axial velocity m/s
\(u_m\) Blade speed at mean radius m/s
\(\Delta c_u\) Swirl added m/s
\(\beta_1\) Inlet relative flow angle (from the plane of rotation) rad
\(\beta_2\) Outlet relative flow angle rad
\(w_2/w_1\) de Haller ratio (keep above about 0.7) -

Method and standards

Axial fan triangles.

Where it is used

  • Preliminary axial fan design and blade setting.
  • Checking a selection for stall margin.

Common mistakes

  • Designing at the tip radius.
  • Ignoring the hub's blockage of the flow area.

Assumptions and limits

  • No inlet swirl; mean-radius design.

References

  • Euler turbomachine equation for axial fans

Questions and answers

Why does the de Haller ratio matter?

It measures how much the relative flow slows through the blade row; too much slowing makes the boundary layer separate and the fan stall.

Why use the root-mean-square radius?

It splits the annulus area in half, so it represents the average blade element reasonably for a first design.

What do the defaults represent?

An illustrative 1.2 m axial fan with a 0.5 m hub at 1,480 rpm moving 15 m³/s against 600 Pa at 85 % hydraulic efficiency.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Bleier, Fan Handbook: Selection, Application and Design (McGraw-Hill, 1998)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.