RC Low-Pass Filter: Cut-Off, Time Constant and Attenuation

Cut-off frequency and time constant of a first-order RC low-pass filter, with its attenuation and phase lag at a chosen frequency.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 10 kΩ, 1 µF against 50 Hz1 kΩ, 100 nF at 10 kHz

Results

A first-order filter attenuates 20 dB per decade above cut-off. Every filter adds lag: keep the time constant well below the control loop's dead time.

Cut-off frequency (−3 dB)1,591.5Hz
Time constant1.0000e-04s
Gain at f0.15718
Attenuation at f (dB)16.072
Phase lag at f80.957°

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 kΩ, 1 µF against 50 Hz. The inputs, in the units selected above:

InputValue
Resistance10,000 Ω
Capacitance1.0000 µF
Signal or noise frequency50.000 Hz

Applying the formula below gives:

ResultValue
Cut-off frequency (−3 dB)15.915 Hz
Time constant0.010000 s
Gain at f0.30331
Attenuation at f (dB)10.362
Phase lag at f72.343 °

Open this example in the calculator and change any input.

Formula

\(f_c = \frac{1}{2\pi RC}, \quad |G| = \frac{1}{\sqrt{1 + (f/f_c)^2}}, \quad \phi = \arctan\frac{f}{f_c}\)

Variables

Symbol Meaning SI unit
\(R\) Resistance Ω
\(C\) Capacitance F
\(f\) Signal or noise frequency 1/s
\(f_c\) Cut-off frequency (−3 dB) 1/s
\(\tau\) Time constant s
\(|G|\) Gain at f -
\(A\) Attenuation at f (dB) -
\(\phi\) Phase lag at f rad

Method and standards

First-order response.

Where it is used

  • Signal conditioning and noise filtering.
  • Choosing transmitter damping.

Common mistakes

  • Filtering more than needed.
  • Ignoring loading by the next stage.

Assumptions and limits

  • Unloaded first-order RC.

References

  • First-order RC low-pass filter (circuit theory definitions)

Questions and answers

How much does a filter attenuate 50 Hz pickup?

A 0.01 s time constant (16 Hz cut-off) cuts 50 Hz by about 10 dB, a factor of three.

Why not filter heavily?

Filtering adds lag to the measurement and can destabilise or slow a control loop.

What do the defaults represent?

A 10 kΩ, 1 µF filter facing 50 Hz noise.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.