Worked example
Example: 13 Hz sampled at 10 Hz. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Sampling rate | 10.000 Hz |
| Signal frequency | 13.000 Hz |
| Highest frequency of interest | 2.0000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Nyquist frequency f_s / 2 | 5.0000 Hz |
| Apparent (alias) frequency | 3.0000 Hz |
| Lowest sampling rate for the bandwidth 2B | 4.0000 Hz |
Open this example in the calculator and change any input.
Formula
\(f_N = \frac{f_s}{2}, \quad f_a = |f - k f_s|,\ k = \text{round}(f/f_s), \quad f_{s,min} = 2B\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f_s\) | Sampling rate | 1/s |
| \(f\) | Signal frequency | 1/s |
| \(B\) | Highest frequency of interest | 1/s |
| \(f_N\) | Nyquist frequency f_s / 2 | 1/s |
| \(f_a\) | Apparent (alias) frequency | 1/s |
| \(f_{s,min}\) | Lowest sampling rate for the bandwidth 2B | 1/s |
Method and standards
Sampling theorem.
Where it is used
- Data logging and PLC scan rates.
- Vibration acquisition.
Common mistakes
- No anti-aliasing filter.
- Sampling exactly at 2B.
Assumptions and limits
- Ideal sampling.
References
- Nyquist–Shannon sampling theorem
Questions and answers
A 13 Hz signal sampled at 10 Hz appears at?
3 Hz.
What sampling rate for 2 Hz content?
At least 4 Hz; in practice 5 to 10 times the bandwidth.
Why does a PLC show a slow wave on a fast signal?
Aliasing: the scan rate is too slow for the signal.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.