Gas DP Flowmeter Pressure and Temperature Compensation

Corrected flow of a gas through an orifice or other DP meter when the line pressure and temperature differ from the design values, for volume and mass flow.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Design 7 bar(a) 30 °C, actual 6 bar(a) 45 °CCompressed air design 8 bar(a) 20 °C, actual 9 bar(a) 35 °CNatural gas 40 bar(a), Z ratio 1.02

Results

The meter reads √(Δp/ρ_design); the true flow follows the actual density, ρ ∝ p/(Z T). Expansibility and Reynolds-number changes are ignored.

Correction for standard volume or mass flow √(p T_d Z_d / (p_d T Z))0.96655
Corrected standard volume or mass flow19,331
Correction for actual volume flow √(p_d T Z / (p T_d Z_d))1.0346
Corrected actual volume flow20,692

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Design 7 bar(a) 30 °C, actual 6 bar(a) 45 °C. The inputs, in the units selected above:

InputValue
Indicated flow (at design conditions)1,000.0 -
Design pressure (absolute; shown as gauge, converted with 1.01325 bar)5.9867 bar g
Design temperature30.000 °C
Actual pressure (absolute; shown as gauge, converted with 1.01325 bar)4.9867 bar g
Actual temperature45.000 °C
Compressibility ratio (design / actual)1.0000 -

Applying the formula below gives:

ResultValue
Correction for standard volume or mass flow √(p T_d Z_d / (p_d T Z))0.90373
Corrected standard volume or mass flow903.73
Correction for actual volume flow √(p_d T Z / (p T_d Z_d))1.1065
Corrected actual volume flow1,106.5

Open this example in the calculator and change any input.

Formula

\(Q_N = Q_{ind}\sqrt{\frac{p\, T_d\, Z_d}{p_d\, T\, Z}}, \quad Q_a = Q_{ind}\sqrt{\frac{p_d\, T\, Z}{p\, T_d\, Z_d}}\)

Variables

Symbol Meaning SI unit
\(Q_{ind}\) Indicated flow (at design conditions) -
\(p_d\) Design pressure (absolute; shown as gauge, converted with 1.01325 bar) Pa
\(T_d\) Design temperature K
\(p\) Actual pressure (absolute; shown as gauge, converted with 1.01325 bar) Pa
\(T\) Actual temperature K
\(Z_d/Z\) Compressibility ratio (design / actual) -
\(k_N\) Correction for standard volume or mass flow √(p T_d Z_d / (p_d T Z)) -
\(Q_N\) Corrected standard volume or mass flow -
\(k_a\) Correction for actual volume flow √(p_d T Z / (p T_d Z_d)) -
\(Q_a\) Corrected actual volume flow -

Method and standards

Density correction of the square-root flow equation.

Where it is used

  • DCS flow compensation blocks.
  • Fuel gas and compressed air metering.

Common mistakes

  • Gauge pressure in the ratio.
  • Applying the factor squared.

Assumptions and limits

  • Ideal gas with a Z ratio; same Δp.
  • Pressures are absolute; the gauge display is converted with the standard atmosphere, not the site barometer (enter absolute at altitude).
  • Read Q_N if the meter is scaled in standard volume or mass flow, Q_a if it is scaled in actual volume flow.

References

  • Ideal-gas density correction of a DP meter: q_m ∝ √(ρ Δp)

Questions and answers

Design 7 bar(a), 30 °C; actual 6 bar(a), 45 °C: how wrong is the reading?

Standard flow factor √(6/7 × 303.15/318.15) = 0.9037: the meter reads 10.7 % high.

Mass or standard volume?

Both take the same factor; actual volume takes the inverse.

Do I need compressibility?

Near ambient, no; at high pressure, yes.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.