Worked example
Example: 200 mm pipe, 120 mm throat, 25 kPa water. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Differential pressure | 25.000 kPa |
| Pipe inside diameter | 200.00 mm |
| Throat diameter | 120.00 mm |
| Density | 998.00 kg/m³ |
| Viscosity | 1.0000 cP |
Applying the formula below gives:
| Result | Value |
|---|---|
| Diameter ratio | 0.60000 |
| Discharge coefficient | 0.96165 |
| Pipe Reynolds number | 524,254 |
| Volume flow | 297.05 m³/h |
| Mass flow | 296.46 t/h |
Open this example in the calculator and change any input.
Formula
\(Q = \frac{C}{\sqrt{1 - \beta^4}}\frac{\pi d^2}{4}\sqrt{\frac{2\Delta p}{\rho}}, \quad C = 0.9900 - 0.2262\beta^{4.1} - (0.00175\beta^2 - 0.0033\beta^{4.15})\left(\frac{10^6}{Re_D}\right)^{1.15}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\Delta p\) | Differential pressure | Pa |
| \(D\) | Pipe inside diameter | m |
| \(d\) | Throat diameter | m |
| \(\rho\) | Density | kg/m³ |
| \(\mu\) | Viscosity | Pa·s |
| \(\beta\) | Diameter ratio | - |
| \(C\) | Discharge coefficient | - |
| \(Re_D\) | Pipe Reynolds number | - |
| \(Q\) | Volume flow | m³/s |
| \(\dot m\) | Mass flow | kg/s |
Method and standards
ISA 1932 nozzle.
Where it is used
- Feedwater and condensate flow.
- Checking nozzle calibration.
Common mistakes
- Using an orifice C.
- Ignoring the range limits.
Assumptions and limits
- Incompressible flow; standard installation.
- The range check is 0.3 ≤ β ≤ 0.8 and 2×10⁴ ≤ Re_D ≤ 10⁷. ISO 5167-3 is tighter for β below 0.44 (a higher lower Reynolds-number limit) and for pipes outside about 50–500 mm; a note appears in those cases.
References
- ISA 1932 nozzle discharge coefficient C = 0.9900 − 0.2262β^4.1 − (0.00175β² − 0.0033β^4.15)(10⁶/Re_D)^1.15 (ISO 5167-3 form)
Questions and answers
Why a nozzle instead of an orifice?
Lower permanent pressure loss than an orifice for the same differential, and it resists erosion: common for boiler feedwater and high-velocity flows.
Why iterate?
The discharge coefficient depends on Reynolds number, which depends on the flow being calculated.
What do the defaults represent?
Water through a 200 mm pipe with a 120 mm throat at 25 kPa differential.