Load Sharing of Two Transformers in Parallel

Share of a total load carried by each of two transformers in parallel from their ratings and percentage impedances, and the largest load without overloading.

Thermal power plantProcess steam and utilities

Inputs

Examples: 1 000 kVA 5 % with 630 kVA 4 %, 1 500 kVA loadTwo equal 500 kVA 4.5 %, 800 kVA2 MVA 6 % with 1 MVA 5 %, 2.5 MVA

Results

Equal voltage ratios and equal X/R ratios are assumed; unequal ratios add a circulating current.

One transformer is overloaded at this total load.

Load on transformer 1839.16kVA
Load on transformer 2660.84kVA
Loading of transformer 183.916%
Loading of transformer 2104.90%
Largest total load without overloading either1,430.0kVA

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 000 kVA 5 % with 630 kVA 4 %, 1 500 kVA load. The inputs, in the units selected above:

InputValue
Rating of transformer 11,000.0 kVA
Percentage impedance of transformer 15.0000 %
Rating of transformer 2630.00 kVA
Percentage impedance of transformer 24.0000 %
Total load1,500.0 kVA

Applying the formula below gives:

ResultValue
Load on transformer 1839.16 kVA
Load on transformer 2660.84 kVA
Loading of transformer 183.916 %
Loading of transformer 2104.90 %
Largest total load without overloading either1,430.0 kVA

Open this example in the calculator and change any input.

Formula

\(S_{L1} = S\, \frac{S_1 / z_1}{S_1/z_1 + S_2/z_2}, \quad S_{max} = \min(z_1, z_2) \left(\frac{S_1}{z_1} + \frac{S_2}{z_2}\right)\)

Variables

Symbol Meaning SI unit
\(S_1\) Rating of transformer 1 VA
\(z_1\) Percentage impedance of transformer 1 -
\(S_2\) Rating of transformer 2 VA
\(z_2\) Percentage impedance of transformer 2 -
\(S\) Total load VA
\(S_{L1}\) Load on transformer 1 VA
\(S_{L2}\) Load on transformer 2 VA
\(u_1\) Loading of transformer 1 -
\(u_2\) Loading of transformer 2 -
\(S_{max}\) Largest total load without overloading either VA

Method and standards

Parallel impedances on a common base.

Where it is used

  • Adding a transformer to a substation.
  • Electrical examinations.

Common mistakes

  • Sharing in proportion to rating only.
  • Ignoring tap differences.

Assumptions and limits

  • Same ratio, vector group and X/R.

References

  • Load division in inverse proportion to ohmic impedance (M.G. Say; IEC 60076-8 application guide)

Questions and answers

How do 1000 kVA at 5 % and 630 kVA at 4 % share 1500 kVA?

839 kVA and 661 kVA: the 630 kVA unit is at 105 %.

Why is the smaller one overloaded?

Its lower percentage impedance makes it take more than its share.

What total is safe?

1430 kVA, when the lower-impedance unit reaches its rating.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.