Transformer Losses, Efficiency and All-Day Efficiency

Efficiency of a transformer at any load from its no-load and load losses, the load for maximum efficiency, all-day efficiency and the energy lost in a year.

Thermal power plantProcess steam and utilitiesElectric motor

Inputs

Examples: 1 000 kVA, 1.7 kW / 10.5 kW losses, 75 % load at 0.9 pf, 16 h2 500 kVA, 3.2 / 22 kW, 50 % at 0.85, 24 h250 kVA, 0.55 / 3.5 kW, 90 % at 0.95, 8 h

Results

Losses at reference temperature; the load loss rises with winding temperature, and harmonics add stray losses.

Efficiency at the load98.441%
Total loss at the load3.3850kW
Load share for maximum efficiency39.641%
Maximum efficiency (same power factor)98.845%
All-day efficiency97.945%
Energy lost per year13,096kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 000 kVA, 1.7 kW / 10.5 kW losses, 75 % load at 0.9 pf, 16 h. The inputs, in the units selected above:

InputValue
Rated power1,000.0 kVA
No-load (core) loss1.7000 kW
Load (copper) loss at rated current10.500 kW
Load as a share of rating75.000 %
Load power factor0.90000 -
Hours per day at that load (energised the rest of the day)16.000 h

Applying the formula below gives:

ResultValue
Efficiency at the load98.886 %
Total loss at the load7.6063 kW
Load share for maximum efficiency40.237 %
Maximum efficiency (same power factor)99.070 %
All-day efficiency98.763 %
Energy lost per year49,384 kWh

Open this example in the calculator and change any input.

Formula

\(\eta = \frac{x S_r \cos\varphi}{x S_r \cos\varphi + P_0 + x^2 P_k}\)

\(x_{max} = \sqrt{P_0 / P_k}\)

\(\eta_{ad} = \frac{x S_r \cos\varphi\, t_L}{x S_r \cos\varphi\, t_L + P_0 \cdot 24\,\text{h} + x^2 P_k t_L}\)

Variables

Symbol Meaning SI unit
\(S_r\) rated power VA
\(P_0\) no-load (core) loss W
\(P_k\) load loss at rated current W
\(x\) load as a share of rating -
\(\cos\varphi\) load power factor -
\(t_L\) hours per day at that load s
\(\eta\) efficiency at the load -
\(P_L\) total loss at the load W
\(x_{max}\) load for maximum efficiency -
\(\eta_{max}\) maximum efficiency -
\(\eta_{ad}\) all-day efficiency -
\(E_L\) energy lost per year J

Method and standards

No-load loss is constant whenever the transformer is energised; load loss varies with the square of the load current. Efficiency is output over output plus losses; maximum efficiency occurs where the two losses are equal. All-day efficiency counts 24 hours of core loss against the hours at load.

Where it is used

  • Comparing transformer offers by loss capitalisation.
  • Deciding whether to switch off lightly loaded parallel transformers.
  • Estimating yearly transformer energy losses.

Common mistakes

  • Using the load loss at a different reference temperature.
  • Comparing efficiencies at different power factors.
  • Forgetting the core loss runs all year.

Assumptions and limits

  • Losses from the test report at reference temperature.
  • Harmonic and stray losses not included.
  • One load level per day; rest of the day energised at no load.

References

  • Transformer loss model (no-load loss constant, load loss ∝ load²)

Questions and answers

How efficient is a 1 000 kVA transformer at 75 % load?

With 1.7 kW no-load and 10.5 kW load losses at 0.9 power factor, 98.9 %. It peaks at 99.07 % at about 40 % load, where load loss equals no-load loss.

What is all-day efficiency?

Energy out over energy in through a day, counting the core loss for all 24 hours; it matters for distribution transformers that are energised all day but loaded only part of it.

How much energy does the transformer waste in a year?

In the example about 49 400 kWh: the core loss runs all year and the load loss only when loaded.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.