FireCADCalc

Transformer All-Day (Energy) Efficiency

All-day (energy) efficiency of a transformer over a daily load cycle of up to four periods, from rating and losses, with the maximum-efficiency load.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 500 kVA, three periodsLightly loaded 1 MVA

Results

Core loss runs all 24 hours whenever the transformer is energised (hours not entered count as no-load); copper loss follows load squared. Distribution transformers with long light-load hours benefit from low core loss.

Energy delivered per day5,400.0kWh
Energy lost per day64.740kWh
All-day efficiency98.815%
Load fraction for maximum efficiency40.237%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 500 kVA, three periods. The inputs, in the units selected above:

InputValue
Rating500.00 kVA
No-load (core) loss1.0000 kW
Full-load copper loss5.5000 kW
Load in period 1 (pu)100.00 %
Duration of period 16.0000 h
Power factor 180.000 %
Load in period 2 (pu)50.000 %
Duration of period 210.000 h
Power factor 285.000 %
Load in period 3 (pu)10.000 %
Duration of period 38.0000 h
Power factor 390.000 %
Load in period 4 (pu)0 %
Duration of period 40 h
Power factor 490.000 %

Applying the formula below gives:

ResultValue
Energy delivered per day4,885.0 kWh
Energy lost per day71.190 kWh
All-day efficiency98.564 %
Load fraction for maximum efficiency42.640 %

Open this example in the calculator and change any input.

Formula

\(\eta_{ad} = \frac{\sum x_iS\cos\phi_it_i}{\sum x_iS\cos\phi_it_i + P_0 t_{day} + \sum x_i^2P_kt_i}, \quad x_{\eta,max} = \sqrt{\frac{P_0}{P_k}}\)

Variables

Symbol Meaning SI unit
\(S\) Rating VA
\(P_0\) No-load (core) loss W
\(P_k\) Full-load copper loss W
\(x_1\) Load in period 1 (pu) -
\(t_1\) Duration of period 1 s
\(\cos\phi_1\) Power factor 1 -
\(x_2\) Load in period 2 (pu) -
\(t_2\) Duration of period 2 s
\(\cos\phi_2\) Power factor 2 -
\(x_3\) Load in period 3 (pu) -
\(t_3\) Duration of period 3 s
\(\cos\phi_3\) Power factor 3 -
\(x_4\) Load in period 4 (pu) -
\(t_4\) Duration of period 4 s
\(\cos\phi_4\) Power factor 4 -
\(E_{out}\) Energy delivered per day J
\(E_{loss}\) Energy lost per day J
\(\eta_{ad}\) All-day efficiency -
\(x_{\eta,max}\) Load fraction for maximum efficiency -
\(t_{day}\) One day (24 h) s

Method and standards

Energy balance.

Where it is used

  • Transformer purchase evaluation.
  • Energy audits of distribution networks.

Common mistakes

  • Ignoring idle hours for core loss.
  • Using full-load efficiency for energy.

Assumptions and limits

  • The transformer is energised all day: hours not covered by the periods count as no-load, with core loss only. The periods must not add to more than 24 h.

  • Constant load within each period.

References

  • Chapman
  • Electric Machinery Fundamentals
  • 5th ed. (McGraw-Hill, 2012)
  • ch. 2 (transformer efficiency; all-day efficiency)

Questions and answers

Why all-day efficiency?

A distribution transformer is energised all day but loaded only part of it; its energy efficiency matters more than its full-load efficiency.

When is efficiency highest?

At the load where copper loss equals core loss: x = √(P₀/P_k).

What do the defaults represent?

A 500 kVA transformer with 1 kW core and 5.5 kW copper loss on a three-period daily cycle.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.