Worked example
Example: 6 % on 2 MVA to 100 MVA at 11 kV. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Impedance on the old base | 6.0000 % |
| Old base power | 2.0000 MVA |
| Old base voltage | 11.000 kV |
| New base power | 100.00 MVA |
| New base voltage | 11.000 kV |
Applying the formula below gives:
| Result | Value |
|---|---|
| Impedance on the new base | 300.00 % |
| Base impedance (new base) | 1.2100 Ω |
| Base current (new base) | 5,248.6 A |
| Impedance in ohms | 3.6300 Ω |
Open this example in the calculator and change any input.
Formula
\(Z_{pu,new} = Z_{pu,old}\, \frac{S_{new}}{S_{old}} \left(\frac{V_{old}}{V_{new}}\right)^2, \quad Z_b = \frac{V^2}{S}, \quad I_b = \frac{S}{\sqrt 3\, V}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Z_{pu,old}\) | Impedance on the old base | - |
| \(S_{old}\) | Old base power | VA |
| \(V_{old}\) | Old base voltage | V |
| \(S_{new}\) | New base power | VA |
| \(V_{new}\) | New base voltage | V |
| \(Z_{pu,new}\) | Impedance on the new base | - |
| \(Z_b\) | Base impedance (new base) | Ω |
| \(I_b\) | Base current (new base) | A |
| \(Z\) | Impedance in ohms | Ω |
Method and standards
Per-unit definitions, three-phase bases.
Where it is used
- Fault level studies.
- Power system examinations.
Common mistakes
- Forgetting the voltage-squared term.
- Mixing kV and V.
Assumptions and limits
- Three-phase power and line voltage bases.
References
- Per-unit system (Stevenson, Elements of Power System Analysis)
Questions and answers
What is a 6 % impedance on 2 MVA when put on a 100 MVA base?
0.06 × 100/2 = 3.0 per unit at the same voltage.
What is the base impedance at 11 kV, 100 MVA?
11² / 100 = 1.21 Ω.
Why per unit?
Impedances of equipment at different voltages can be added directly.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.