Neutral Earthing Resistor: Resistance, Current and Energy

Neutral earthing resistor resistance, current, power and energy for a rated time, with a check against the system's capacitive charging current.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 11 kV, 300 A, 10 s6.6 kV HRG 10 A continuous-like 60 s

Results

Resistance21.170Ω
Power at fault current1,905.3kW
Energy for the rated time19.053MJ
Ratio to charging current15.000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 11 kV, 300 A, 10 s. The inputs, in the units selected above:

InputValue
System line voltage11.000 kV
Earth-fault current limit300.00 A
Rated time10.000 s
System capacitive charging current (3I₀)20.000 A

Applying the formula below gives:

ResultValue
Resistance21.170 Ω
Power at fault current1,905.3 kW
Energy for the rated time19.053 MJ
Ratio to charging current15.000

Open this example in the calculator and change any input.

Formula

\(R = \frac{V/\sqrt3}{I_{NER}}, \quad P = \frac{V}{\sqrt3}I_{NER}, \quad E = Pt\)

Variables

Symbol Meaning SI unit
\(V\) System line voltage V
\(I_{NER}\) Earth-fault current limit A
\(t\) Rated time s
\(3I_{c0}\) System capacitive charging current (3I₀) A
\(R\) Resistance Ω
\(P\) Power at fault current W
\(E\) Energy for the rated time J
\(I_{NER}/3I_{c0}\) Ratio to charging current -

Method and standards

Ohm's law and energy.

Where it is used

  • Generator and transformer neutral earthing.
  • MV system design.

Common mistakes

  • Using line voltage across the resistor.
  • Rating for continuous duty when 10 s suffices.

Assumptions and limits

  • Single phase-to-earth fault; resistor dominates.
  • The ratio to charging current is shown only when a charging current is entered.

References

  • Neutral earthing resistor sizing R = V_ph/I_f (definitions; IEEE 32 ratings practice)

Questions and answers

Why limit earth-fault current?

To reduce damage and arc flash at the fault while keeping enough current for reliable relaying.

Why compare with charging current?

If resistor current is lower than system charging current, intermittent arcing faults can build up dangerous overvoltages.

What do the defaults represent?

An 11 kV system limited to 300 A for 10 s, with 20 A charging current.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.