Induction Motor Contribution to a Bus Fault

Initial fault current that running induction motors feed into a nearby bus fault from their total rating, locked-rotor current ratio and the decay over a few cycles.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 2 MW LV motors at 415 V6.6 kV motors 5 MW

Results

Induction motors contribute roughly their locked-rotor current for the first cycle, decaying within a few cycles as their flux collapses. Include them in breaker making and busbar duties.

Total rated current3,478.0A
Initial motor contribution20.868kA
Contribution at t10.714kA

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 MW LV motors at 415 V. The inputs, in the units selected above:

InputValue
Total running motor power2,000.0 kW
Bus line voltage415.00 V
Efficiency × power factor80.000 %
Locked-rotor current ratio6.0000 -
Decay time constant0.030000 s
Time after fault0.020000 s

Applying the formula below gives:

ResultValue
Total rated current3,478.0 A
Initial motor contribution20.868 kA
Contribution at t10.714 kA

Open this example in the calculator and change any input.

Formula

\(I_r = \frac{P}{\sqrt3V\eta\cos\phi}, \quad I_m(t) = \frac{I_{LR}}{I_r}I_re^{-t/\tau}\)

Variables

Symbol Meaning SI unit
\(P\) Total running motor power W
\(V\) Bus line voltage V
\(\eta\cos\phi\) Efficiency × power factor -
\(I_{LR}/I_r\) Locked-rotor current ratio -
\(\tau\) Decay time constant s
\(t\) Time after fault s
\(I_r\) Total rated current A
\(I_m(0)\) Initial motor contribution A
\(I_m(t)\) Contribution at t A

Method and standards

Locked-rotor approximation.

Where it is used

  • LV switchboard ratings.
  • MCC breaker selection.

Common mistakes

  • Ignoring motors in short-circuit studies.
  • Counting standby motors.

Assumptions and limits

  • Running motors only. The symmetrical AC envelope only: the DC offset that adds to the peak (making duty) is not included.
  • τ is the motor's open-circuit subtransient decay, X″/(ωR_r) from the maker; typically a few cycles for LV motors, longer for large HV motors.

References

  • Motor contribution approximated by locked-rotor current with exponential decay (definitions; Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012))

Questions and answers

Why do motors feed a fault?

Their rotors keep spinning and their trapped flux makes them act briefly as generators.

How large is it?

About 4–6 times the total motor rated current for the first cycle.

What do the defaults represent?

2 MW of running LV motors on a 415 V bus.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.