Generator Short-Circuit Current: Subtransient to Steady State

Three-phase short-circuit current of a synchronous generator over time from its rating and subtransient, transient and synchronous reactances and time constants.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 10 MVA, 11 kV at 100 ms50 MVA, 11 kV at 0 s

Results

Symmetrical rms envelope; DC offset is extra. With an AVR and field forcing, sustained current can be 2–4 times rated instead of E/x_d.

Rated current2,624.3A
Initial subtransient current15.309kA
Transient current9.8412kA
Sustained current (no AVR boost)1.3778kA
Symmetrical rms current at t15.309kA

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 MVA, 11 kV at 100 ms. The inputs, in the units selected above:

InputValue
Generator rating10.000 MVA
Rated line voltage11.000 kV
Subtransient reactance (per unit)0.15000 -
Transient reactance (per unit)0.25000 -
Synchronous reactance (per unit)1.8000 -
Subtransient time constant0.035000 s
Transient time constant1.0000 s
Time after fault0.10000 s
Internal voltage before fault (per unit)1.0000 -

Applying the formula below gives:

ResultValue
Rated current524.86 A
Initial subtransient current3.4991 kA
Transient current2.0995 kA
Sustained current (no AVR boost)0.29159 kA
Symmetrical rms current at t2.0078 kA

Open this example in the calculator and change any input.

Formula

\(I(t) = (I'' - I')e^{-t/T''_d} + (I' - I_{ss})e^{-t/T'_d} + I_{ss}, \quad I'' = \frac{E}{x''_d}I_r\)

Variables

Symbol Meaning SI unit
\(S\) Generator rating VA
\(V\) Rated line voltage V
\(x''_d\) Subtransient reactance (per unit) -
\(x'_d\) Transient reactance (per unit) -
\(x_d\) Synchronous reactance (per unit) -
\(T''_d\) Subtransient time constant s
\(T'_d\) Transient time constant s
\(t\) Time after fault s
\(E\) Internal voltage before fault (per unit) -
\(I_r\) Rated current A
\(I''\) Initial subtransient current A
\(I'\) Transient current A
\(I_{ss}\) Sustained current (no AVR boost) A
\(I(t)\) Symmetrical rms current at t A

Method and standards

Decrement curve.

Where it is used

  • Captive power plant protection.
  • Breaker and relay checks near generators.

Common mistakes

  • Using x_d for breaker duty.
  • Ignoring the DC component.

Assumptions and limits

  • Three-phase fault at terminals; constant field voltage.
  • One internal voltage E for all three periods (the textbook simplification for a fault from no load); from loaded conditions E″ and E′ differ.

References

  • Chapman
  • Electric Machinery Fundamentals
  • 5th ed. (McGraw-Hill, 2012)
  • ch. 4 (short-circuit transients in synchronous generators)

Questions and answers

Why does generator fault current fall with time?

Damper and field windings first oppose the flux change (subtransient), then decay; the steady value is set by synchronous reactance.

Why can sustained current be too low to trip relays?

E/x_d is often below rated current without AVR boost; protection must act in the transient period or use voltage-restrained relays.

What do the defaults represent?

A 10 MVA, 11 kV generator with typical reactances, 100 ms after the fault.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators