Worked example
Example: 10 MVA, 11 kV at 100 ms. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Generator rating | 10.000 MVA |
| Rated line voltage | 11.000 kV |
| Subtransient reactance (per unit) | 0.15000 - |
| Transient reactance (per unit) | 0.25000 - |
| Synchronous reactance (per unit) | 1.8000 - |
| Subtransient time constant | 0.035000 s |
| Transient time constant | 1.0000 s |
| Time after fault | 0.10000 s |
| Internal voltage before fault (per unit) | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Rated current | 524.86 A |
| Initial subtransient current | 3.4991 kA |
| Transient current | 2.0995 kA |
| Sustained current (no AVR boost) | 0.29159 kA |
| Symmetrical rms current at t | 2.0078 kA |
Open this example in the calculator and change any input.
Formula
\(I(t) = (I'' - I')e^{-t/T''_d} + (I' - I_{ss})e^{-t/T'_d} + I_{ss}, \quad I'' = \frac{E}{x''_d}I_r\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S\) | Generator rating | VA |
| \(V\) | Rated line voltage | V |
| \(x''_d\) | Subtransient reactance (per unit) | - |
| \(x'_d\) | Transient reactance (per unit) | - |
| \(x_d\) | Synchronous reactance (per unit) | - |
| \(T''_d\) | Subtransient time constant | s |
| \(T'_d\) | Transient time constant | s |
| \(t\) | Time after fault | s |
| \(E\) | Internal voltage before fault (per unit) | - |
| \(I_r\) | Rated current | A |
| \(I''\) | Initial subtransient current | A |
| \(I'\) | Transient current | A |
| \(I_{ss}\) | Sustained current (no AVR boost) | A |
| \(I(t)\) | Symmetrical rms current at t | A |
Method and standards
Decrement curve.
Where it is used
- Captive power plant protection.
- Breaker and relay checks near generators.
Common mistakes
- Using x_d for breaker duty.
- Ignoring the DC component.
Assumptions and limits
- Three-phase fault at terminals; constant field voltage.
- One internal voltage E for all three periods (the textbook simplification for a fault from no load); from loaded conditions E″ and E′ differ.
References
- Chapman
- Electric Machinery Fundamentals
- 5th ed. (McGraw-Hill, 2012)
- ch. 4 (short-circuit transients in synchronous generators)
Questions and answers
Why does generator fault current fall with time?
Damper and field windings first oppose the flux change (subtransient), then decay; the steady value is set by synchronous reactance.
Why can sustained current be too low to trip relays?
E/x_d is often below rated current without AVR boost; protection must act in the transient period or use voltage-restrained relays.
What do the defaults represent?
A 10 MVA, 11 kV generator with typical reactances, 100 ms after the fault.