Current Transformer Burden with Lead Resistance

Total burden on a current transformer from the lead length and size and the relay or meter burden, against the CT's rated VA, with the longest lead allowed.

Thermal power plantProcess steam and utilitiesIEC 60364 (low-voltage installations)

Inputs

Examples: 5 A CT, 30 m of 2.5 mm², 1 VA relay, 15 VA CT1 A CT, 200 m of 2.5 mm², 0.5 VA, 5 VA5 A CT, 80 m of 4 mm², 3 VA, 10 VA (overloaded)

Default: copper in service (IEC 60364-5-52 Annex G, 1.25 × the 20 °C value).

Results

Lead resistance, go and return0.54000Ω
Lead burden I_s² R_L13.500VA
Total burden14.500VA
Share of the rated burden used96.667%
Longest one-way lead for the rated burden31.111m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 A CT, 30 m of 2.5 mm², 1 VA relay, 15 VA CT. The inputs, in the units selected above:

InputValue
Rated secondary current5.0000 A
One-way lead length (CT to relay or meter)30.000 m
Lead cross-section2.5000 mm²
Resistivity of the lead at its temperature0.022500 Ω·mm²/m
Burden of the relay or meter at rated current1.0000 VA
Rated burden of the CT15.000 VA

Applying the formula below gives:

ResultValue
Lead resistance, go and return0.54000 Ω
Lead burden I_s² R_L13.500 VA
Total burden14.500 VA
Share of the rated burden used96.667 %
Longest one-way lead for the rated burden31.111 m

Open this example in the calculator and change any input.

Formula

\(R_L = \frac{2 \rho L}{A}, \quad S_L = I_s^2 R_L, \quad S_t = S_L + S_b\)

Variables

Symbol Meaning SI unit
\(I_s\) Rated secondary current A
\(L\) One-way lead length (CT to relay or meter) m
\(A\) Lead cross-section m²
\(\rho\) Resistivity of the lead at its temperature Ω·m
\(S_b\) Burden of the relay or meter at rated current VA
\(S_n\) Rated burden of the CT VA
\(R_L\) Lead resistance, go and return Ω
\(S_L\) Lead burden I_s² R_L VA
\(S_t\) Total burden VA
\(u\) Share of the rated burden used -
\(L_{max}\) Longest one-way lead for the rated burden m

Method and standards

Joule burden of the secondary loop.

Where it is used

  • Selecting CT VA for panels and switchyards.
  • Checking long CT runs.

Common mistakes

  • Counting the lead one way.
  • Ignoring connected meters in series.

Assumptions and limits

  • Resistive burden; power factor of burdens ignored.
  • A total under 25 % of the rated burden is flagged for metering CTs.

References

  • Burden = I² R (IEC 61869-2 terminology)
  • IEC 60364-5-52 Annex G (conductor resistivity in service)

Questions and answers

What burden do 30 m of 2.5 mm² leads add on a 5 A CT?

R = 0.54 Ω, so 13.5 VA; with a 1 VA relay 14.5 VA of a 15 VA CT.

Why use a 1 A secondary for long runs?

Lead burden goes with current squared: 25 times less than at 5 A.

Is too little burden a problem?

For metering CTs accuracy is specified between 25 % and 100 % of rated burden.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.