Busbar Short-Circuit Force Between Conductors

Electromagnetic force between parallel busbars or cables during a short circuit from the peak current and spacing, per metre and on a support span.

Thermal power plantProcess steam and utilities

Inputs

Examples: 105 kA peak, 100 mm, 0.6 m span, three phase40 kA peak, 60 mm, 0.4 m, two conductors220 kA peak, 250 mm, 1 m, three phase

Results

Long, thin, parallel conductors (spacing well above the bar size). Bar-shape factors, resonance and the stress in the bars and insulators are design checks to IEC 60865-1 and are not done here.

Force per unit length33.533kN/m
Force on one span33.533kN

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 105 kA peak, 100 mm, 0.6 m span, three phase. The inputs, in the units selected above:

InputValue
Peak short-circuit current105.00 kA
Centre-to-centre spacing of the conductors100.00 mm
Span between supports0.60000 m
ArrangementThree phase, side by side (centre conductor)

Applying the formula below gives:

ResultValue
Force per unit length19.096 kN/m
Force on one span11.458 kN

Open this example in the calculator and change any input.

Formula

\(F' = \frac{\mu_0}{2\pi}\, \frac{i_p^2}{a}\ \left(\times \frac{\sqrt 3}{2}\ \text{three phase}\right), \quad F = F'\, l\)

Variables

Symbol Meaning SI unit
\(i_p\) Peak short-circuit current A
\(a\) Centre-to-centre spacing of the conductors m
\(l\) Span between supports m
\(\text{type}\) Arrangement -
\(F'\) Force per unit length N/m
\(F\) Force on one span N

Method and standards

Force between parallel current-carrying conductors.

Where it is used

  • Busbar support spacing checks.
  • Cable cleat selection.

Common mistakes

  • Using RMS instead of peak current.
  • Spacing in mm in an SI formula.

Assumptions and limits

  • Thin parallel conductors; static force.
  • No conductor-shape factor (k₁s of IEC 60865-1) for rectangular bars close together: the result is the basic force between line currents.

References

  • Ampère's force law
  • F' = μ₀ i² / (2π a); three-phase centre conductor factor √3/2 (the basic relation of IEC 60865-1)

Questions and answers

What force acts between busbars 100 mm apart at 105 kA peak, three phase?

19.1 kN/m; on a 0.6 m span 11.5 kN.

Which current?

The peak (making) current, about 2.1 to 2.5 times the RMS symmetrical fault current.

Why the √3/2?

It is the largest force on the centre bar of three in a three-phase fault.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.