Unified Glare Rating (UGR) for up to Three Luminaires

Discomfort glare rating from background luminance and each luminaire's luminance, solid angle and Guth position index, by the UGR formula.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative two LED panelsBright downlights, dark roomHigh bay in a workshop

Accepted: 1 to 1,000
Accepted: 0 to 1,000,000
Accepted: 0 to 0.1
Accepted: 1 to 20
Accepted: 0 to 1,000,000
Accepted: 0 to 0.1
Accepted: 1 to 20
Accepted: 0 to 1,000,000
Accepted: 0 to 0.1
Accepted: 1 to 20

Results

UGR = 8·log₁₀[(0.25/L_b)ΣL²ω/p²]: bright, large luminaires close to the line of sight (small Guth index) dominate. Typical limits are UGR 19 for offices and 22–25 for industrial work; luminaire makers publish UGR tables for standard rooms, which are the usual design route.

Glare sum ΣL²ω/p²254,000
Unified glare rating24.197

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative two LED panels. The inputs, in the units selected above:

InputValue
Background luminance40.000 -
Luminance of luminaire 1 (cd/m²)6,000.0 -
Solid angle of luminaire 1 (sr)0.004000 -
Guth position index 12.5000 -
Luminance of luminaire 26,000.0 -
Solid angle 20.003000 -
Guth index 24.0000 -
Luminance of luminaire 30 -
Solid angle 30 -
Guth index 31.0000 -

Applying the formula below gives:

ResultValue
Glare sum ΣL²ω/p²29,790
Unified glare rating18.160

Open this example in the calculator and change any input.

Formula

\(UGR = 8\log_{10}\left(\frac{0.25}{L_b}\sum\frac{L^2\omega}{p^2}\right)\)

Variables

Symbol Meaning SI unit
\(L_b\) Background luminance -
\(L_1\) Luminance of luminaire 1 (cd/m²) -
\(\omega_1\) Solid angle of luminaire 1 (sr) -
\(p_1\) Guth position index 1 -
\(L_2\) Luminance of luminaire 2 -
\(\omega_2\) Solid angle 2 -
\(p_2\) Guth index 2 -
\(L_3\) Luminance of luminaire 3 -
\(\omega_3\) Solid angle 3 -
\(p_3\) Guth index 3 -
\(\Sigma\) Glare sum ΣL²ω/p² -
\(UGR\) Unified glare rating -

Method and standards

Glare rating.

Where it is used

  • Office and control room lighting design.
  • Comparing luminaire options.

Common mistakes

  • Using luminaire intensity instead of luminance.
  • Taking the Guth index for the wrong viewing direction.

Assumptions and limits

  • Valid for luminaires of solid angle about 0.0003–0.1 sr.

References

  • UGR formula
  • CIE 117
  • Discomfort Glare in Interior Lighting (UGR formula)

Questions and answers

What UGR is acceptable in an office?

19 or below for screen work and reading; workshops often accept 22–25.

Why does background luminance matter?

A brighter background reduces the contrast of the luminaires, lowering glare.

What do the defaults represent?

Two illustrative LED panels at 6,000 cd/m² seen at 0.004 and 0.003 sr with Guth indices 2.5 and 4 against a 40 cd/m² background.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Boyce, Human Factors in Lighting, 3rd ed. (CRC, 2014)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.