FireCADCalc

Illuminance Uniformity from Measured Points

Average, minimum and maximum illuminance and the uniformity ratios from up to nine measured grid points of a lighting survey.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative six readingsNine-point office gridWarehouse aisle 4 points

Accepted: 0 to 100,000 lx
Accepted: 0 to 100,000 lx
Accepted: 0 to 100,000 lx
Accepted: 0 to 100,000 lx
Accepted: 0 to 100,000 lx
Accepted: 0 to 100,000 lx
Accepted: 0 to 100,000 lx
Accepted: 0 to 100,000 lx
Accepted: 0 to 100,000 lx

Results

Readings of zero are treated as not taken. Measure on a regular grid over the task area at working-plane height; guidance commonly asks for U₀ of about 0.4–0.7 depending on the task.

Points used6.0000
Average illuminance501.67lx
Minimum390.00lx
Maximum610.00lx
Uniformity E_min/Ē77.741%
Diversity E_min/E_max63.934%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative six readings. The inputs, in the units selected above:

InputValue
Point 1520.00 lx
Point 2480.00 lx
Point 3610.00 lx
Point 4450.00 lx
Point 5560.00 lx
Point 6 (0 = not measured)390.00 lx
Point 7 (0 = not measured)0 lx
Point 8 (0 = not measured)0 lx
Point 9 (0 = not measured)0 lx

Applying the formula below gives:

ResultValue
Points used6.0000
Average illuminance501.67 lx
Minimum390.00 lx
Maximum610.00 lx
Uniformity E_min/Ē77.741 %
Diversity E_min/E_max63.934 %

Open this example in the calculator and change any input.

Formula

\(\bar E = \frac{1}{n}\sum E_i, \quad U_0 = \frac{E_{min}}{\bar E}, \quad U_d = \frac{E_{min}}{E_{max}}\)

Variables

Symbol Meaning SI unit
\(E_1\) Point 1 lx
\(E_2\) Point 2 lx
\(E_3\) Point 3 lx
\(E_4\) Point 4 lx
\(E_5\) Point 5 lx
\(E_6\) Point 6 (0 = not measured) lx
\(E_7\) Point 7 (0 = not measured) lx
\(E_8\) Point 8 (0 = not measured) lx
\(E_9\) Point 9 (0 = not measured) lx
\(n\) Points used -
\(\bar E\) Average illuminance lx
\(E_{min}\) Minimum lx
\(E_{max}\) Maximum lx
\(U_0\) Uniformity E_min/Ē -
\(U_d\) Diversity E_min/E_max -

Method and standards

Uniformity.

Where it is used

  • Lighting commissioning and audits.
  • Comparing design and site measurements.

Common mistakes

  • Measuring only under luminaires.
  • Mixing readings at different heights.

Assumptions and limits

  • Equal-area grid points.

References

  • Lighting survey statistics
  • Grid measurement of illuminance

Questions and answers

Why does uniformity matter?

Large differences across a work area make the eye keep re-adapting, causing fatigue and hiding hazards in darker patches.

How many points should I measure?

A grid fine enough to catch luminaire spacing, typically 0.5–2 m apart; this sheet takes up to nine points.

What do the defaults represent?

Illustrative readings of 520, 480, 610, 450, 560 and 390 lux at six grid points.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.