Worked example
Example: Illustrative six readings. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Point 1 | 520.00 lx |
| Point 2 | 480.00 lx |
| Point 3 | 610.00 lx |
| Point 4 | 450.00 lx |
| Point 5 | 560.00 lx |
| Point 6 (0 = not measured) | 390.00 lx |
| Point 7 (0 = not measured) | 0 lx |
| Point 8 (0 = not measured) | 0 lx |
| Point 9 (0 = not measured) | 0 lx |
Applying the formula below gives:
| Result | Value |
|---|---|
| Points used | 6.0000 |
| Average illuminance | 501.67 lx |
| Minimum | 390.00 lx |
| Maximum | 610.00 lx |
| Uniformity E_min/Ē | 77.741 % |
| Diversity E_min/E_max | 63.934 % |
Open this example in the calculator and change any input.
Formula
\(\bar E = \frac{1}{n}\sum E_i, \quad U_0 = \frac{E_{min}}{\bar E}, \quad U_d = \frac{E_{min}}{E_{max}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E_1\) | Point 1 | lx |
| \(E_2\) | Point 2 | lx |
| \(E_3\) | Point 3 | lx |
| \(E_4\) | Point 4 | lx |
| \(E_5\) | Point 5 | lx |
| \(E_6\) | Point 6 (0 = not measured) | lx |
| \(E_7\) | Point 7 (0 = not measured) | lx |
| \(E_8\) | Point 8 (0 = not measured) | lx |
| \(E_9\) | Point 9 (0 = not measured) | lx |
| \(n\) | Points used | - |
| \(\bar E\) | Average illuminance | lx |
| \(E_{min}\) | Minimum | lx |
| \(E_{max}\) | Maximum | lx |
| \(U_0\) | Uniformity E_min/Ē | - |
| \(U_d\) | Diversity E_min/E_max | - |
Method and standards
Uniformity.
Where it is used
- Lighting commissioning and audits.
- Comparing design and site measurements.
Common mistakes
- Measuring only under luminaires.
- Mixing readings at different heights.
Assumptions and limits
- Equal-area grid points.
References
- Lighting survey statistics
- Grid measurement of illuminance
Questions and answers
Why does uniformity matter?
Large differences across a work area make the eye keep re-adapting, causing fatigue and hiding hazards in darker patches.
How many points should I measure?
A grid fine enough to catch luminaire spacing, typically 0.5–2 m apart; this sheet takes up to nine points.
What do the defaults represent?
Illustrative readings of 520, 480, 610, 450, 560 and 390 lux at six grid points.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.