Room Index and Cavity Ratios for Lighting Design

Room index and the room, ceiling and floor cavity ratios of a rectangular room from its length, width and the cavity heights, for utilisation factor tables.

Food, dairy and textile

Inputs

Examples: Illustrative 12 x 8 m officeFactory 60 x 30 m high bayNarrow corridor 20 x 2 m

Accepted: 0.5 to 500 m
Accepted: 0.5 to 500 m
Accepted: 0.1 to 50 m
Accepted: 0 to 20 m
Accepted: 0 to 5 m

Results

k = LW/(h_m(L + W)), used with utilisation factor tables; cavity ratios = 5h(L + W)/(LW) for the zonal-cavity method (RCR = 5/k). Small or tall rooms have low k and lose more light to the walls.

Room index2.1818
Room cavity ratio2.2917
Ceiling cavity ratio0.52083
Floor cavity ratio0.83333

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 12 x 8 m office. The inputs, in the units selected above:

InputValue
Room length12.000 m
Room width8.0000 m
Luminaire height above the working plane2.2000 m
Ceiling cavity depth (suspension)0.50000 m
Working plane height above floor0.80000 m

Applying the formula below gives:

ResultValue
Room index2.1818
Room cavity ratio2.2917
Ceiling cavity ratio0.52083
Floor cavity ratio0.83333

Open this example in the calculator and change any input.

Formula

\(k = \frac{LW}{h_m(L + W)}, \quad CR = \frac{5h(L + W)}{LW}\)

Variables

Symbol Meaning SI unit
\(L\) Room length m
\(W\) Room width m
\(h_m\) Luminaire height above the working plane m
\(h_c\) Ceiling cavity depth (suspension) m
\(h_f\) Working plane height above floor m
\(k\) Room index -
\(RCR\) Room cavity ratio -
\(CCR\) Ceiling cavity ratio -
\(FCR\) Floor cavity ratio -

Method and standards

Room index.

Where it is used

  • Lumen-method lighting design.
  • Reading utilisation factor tables.

Common mistakes

  • Measuring height from the floor instead of the working plane.
  • Using the ceiling height in the room index.

Assumptions and limits

  • Rectangular room.

References

  • Room index and zonal-cavity ratios
  • Lighting Handbook practice (lumen method, maintenance factor components)

Questions and answers

What does the room index tell me?

How much light reaches the working plane directly: large shallow rooms (high k) use light efficiently; narrow tall rooms (low k) lose more to the walls.

How do RCR and room index relate?

RCR = 5/k for the same mounting height.

What do the defaults represent?

An illustrative 12 × 8 m office with luminaires 2.2 m above a 0.8 m working plane and 0.5 m suspension.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.