Worked example
Example: Illustrative 40 x 8 W for 3 h at 216 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Number of luminaires | 40.000 - |
| Power per luminaire in emergency mode | 0.008000 kW |
| Rated duration | 3.0000 h |
| Battery voltage | 216.00 V |
| Inverter and wiring efficiency | 85.000 % |
| Ageing factor (end-of-life capacity margin) | 1.2500 - |
| Temperature factor | 1.1000 - |
| Allowed depth of discharge | 80.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total emergency load | 0.32000 kW |
| Energy for the duration | 0.96000 kWh |
| Battery discharge current | 1.7429 A |
| Required battery capacity | 8.9869 Ah |
Open this example in the calculator and change any input.
Formula
\(I = \frac{nP_l}{\eta V}, \quad C = \frac{Itk_ak_t}{DoD}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | Number of luminaires | - |
| \(P_l\) | Power per luminaire in emergency mode | W |
| \(t\) | Rated duration | s |
| \(V\) | Battery voltage | V |
| \(\eta\) | Inverter and wiring efficiency | - |
| \(k_a\) | Ageing factor (end-of-life capacity margin) | - |
| \(k_t\) | Temperature factor | - |
| \(DoD\) | Allowed depth of discharge | - |
| \(P\) | Total emergency load | W |
| \(E\) | Energy for the duration | J |
| \(I\) | Battery discharge current | A |
| \(C\) | Required battery capacity | C |
Method and standards
Emergency battery sizing.
Where it is used
- Central battery and inverter systems.
- Checking existing installations.
Common mistakes
- Ignoring the rate dependence of capacity.
- Forgetting inverter losses.
Assumptions and limits
- Constant power load.
References
- Battery sizing for a constant-power load
Questions and answers
Why add ageing and temperature factors?
Batteries lose capacity with age and cold; sizing for end of life ensures the full duration is still met before replacement.
How long must emergency lighting run?
Often 1 or 3 hours depending on the building and national rules.
What do the defaults represent?
An illustrative 40 luminaires of 8 W for 3 hours from a 216 V battery, 85 % inverter efficiency, ageing 1.25, temperature 1.1 and 80 % depth of discharge.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9