LED Lumen Maintenance Projection and L70 Life

Exponential lumen maintenance fitted through two test points, the projected hours to a lumen maintenance level such as L70 and the output at a chosen time.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 98.5 % and 95.5 % at 1000 and 6000 hHot luminaire, faster decayL80 of a good package

Accepted: 1 to 277,780 h
Accepted: 50 to 110 %
Accepted: 1 to 277,780 h
Accepted: 50 to 110 %
Accepted: 30 to 99 %
Accepted: 1 to 2,777,800 h

Results

Φ(t) = B·e^(−αt) through the two points; L_x = ln(B/x)/α. The standard projection method fits the same exponential by least squares to all data after 1,000 h and limits reported life to six times the test duration; results beyond that are shown as greater than the limit. Driver and luminaire temperature govern real life.

Decay rate6.1861e-061/h
Initial constant0.99111
Projected life to the level56,215h
Lumen maintenance at the time of interest72.744%
Usual extrapolation limit (6 × test duration)36,000h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 98.5 % and 95.5 % at 1000 and 6000 h. The inputs, in the units selected above:

InputValue
First test time1,000.0 h
Lumen maintenance at t₁98.500 %
Second test time6,000.0 h
Lumen maintenance at t₂95.500 %
Maintenance level of interest70.000 %
Time of interest50,000 h

Applying the formula below gives:

ResultValue
Decay rate6.1861e-06 1/h
Initial constant0.99111
Projected life to the level56,215 h
Lumen maintenance at the time of interest72.744 %
Usual extrapolation limit (6 × test duration)36,000 h

Open this example in the calculator and change any input.

Formula

\(\Phi(t) = Be^{-\alpha t}, \quad \alpha = \frac{\ln(\Phi_1/\Phi_2)}{t_2 - t_1}, \quad L_x = \frac{\ln(B/x)}{\alpha}\)

Variables

Symbol Meaning SI unit
\(t_1\) First test time s
\(\Phi_1\) Lumen maintenance at t₁ -
\(t_2\) Second test time s
\(\Phi_2\) Lumen maintenance at t₂ -
\(x\) Maintenance level of interest -
\(t\) Time of interest s
\(\alpha\) Decay rate 1/s
\(B\) Initial constant -
\(L_x\) Projected life to the level s
\(\Phi(t)\) Lumen maintenance at the time of interest -
\(6t_2\) Usual extrapolation limit (6 × test duration) s

Method and standards

Lumen maintenance.

Where it is used

  • Comparing LED products and warranties.
  • Setting maintenance factors.

Common mistakes

  • Quoting life far beyond six times the test duration.
  • Using data before 1,000 h, when output can rise.

Assumptions and limits

  • Exponential decay; same drive current and temperature as the test.

References

  • Exponential lumen maintenance projection
  • IES TM-21
  • Projecting Long Term Lumen Maintenance of LED Light Sources (exponential projection form)

Questions and answers

What does L70 mean?

The operating time until light output falls to 70 % of initial, a common end-of-life definition for LEDs.

Why limit extrapolation to six times the test?

Fitting a short test and projecting far beyond it overstates confidence; the limit keeps claims honest.

What do the defaults represent?

Illustrative test data: 98.5 % at 1,000 h and 95.5 % at 6,000 h, projected to L70 and read at 50,000 h.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.