LED Lighting Retrofit Energy Saving and Payback

Power, energy, cost and CO2 saved by replacing light fittings with LED, with simple payback from the fitting cost and any maintenance saving.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 200 fittings 72 to 36 WWarehouse 400 W HID to 150 W LEDStreet lights 150 to 60 W

Accepted: 1 to 1,000,000
Accepted: 0.001 to 5 kW
Accepted: 0.001 to 5 kW
Accepted: 1 to 8,760 h
Accepted: 0 to 100
Accepted: 0 to 100,000
Accepted: 0 to 10,000
Accepted: 0 to 1.5

Results

Saving = N(P₁ − P₂)·hours; include control gear losses in the present power (a 2 × 36 W fluorescent with magnetic ballast draws about 80–90 W). Check that the LED fittings still meet the illuminance; adding dimming or occupancy controls saves more.

Power saved7.2000kW
Energy saved per year21.600MWh
Cost saved per year3,640.0
Simple payback (years)3.2967
CO₂ avoided per year (t)15.120

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 200 fittings 72 to 36 W. The inputs, in the units selected above:

InputValue
Number of fittings200.00 -
Present power per fitting (with control gear)0.072000 kW
LED power per fitting0.036000 kW
Operating hours per year3,000.0 h
Electricity price per kWh0.15000 -
Installed cost per LED fitting60.000 -
Maintenance saving per fitting per year2.0000 -
Grid emission factor (kg CO₂/kWh)0.70000 -

Applying the formula below gives:

ResultValue
Power saved7.2000 kW
Energy saved per year21.600 MWh
Cost saved per year3,640.0
Simple payback (years)3.2967
CO₂ avoided per year (t)15.120

Open this example in the calculator and change any input.

Formula

\(\Delta E = N(P_1 - P_2)t, \quad t_{pb} = \frac{NC_f}{c_e\Delta E + Nc_m}\)

Variables

Symbol Meaning SI unit
\(N\) Number of fittings -
\(P_1\) Present power per fitting (with control gear) W
\(P_2\) LED power per fitting W
\(t\) Operating hours per year s
\(c_e\) Electricity price per kWh -
\(C_f\) Installed cost per LED fitting -
\(c_m\) Maintenance saving per fitting per year -
\(EF\) Grid emission factor (kg CO₂/kWh) -
\(\Delta P\) Power saved W
\(\Delta E\) Energy saved per year J
\(\Delta C\) Cost saved per year -
\(t_{pb}\) Simple payback (years) -
\(m_{CO_2}\) CO₂ avoided per year (t) -

Method and standards

Retrofit saving.

Where it is used

  • Building energy audits.
  • Street and industrial lighting upgrades.

Common mistakes

  • Ignoring ballast losses in the old fittings.
  • Forgetting reduced cooling load or lower heating gains.

Assumptions and limits

  • Constant hours and tariff; simple payback.

References

  • Lighting retrofit energy balance
  • Lighting Handbook practice (lumen method, maintenance factor components)

Questions and answers

How quickly do LED retrofits pay back?

Often 1–3 years where lights run long hours; much longer for rarely used rooms.

Should I replace lamps or whole fittings?

Whole fittings usually give better optics and efficiency; lamp-only retrofits are cheaper but may leave old drivers or ballasts in circuit.

What do the defaults represent?

An illustrative 200 fittings drawing 72 W replaced by 36 W LED, used 3,000 hours a year at 0.15 per kWh, 60 per fitting installed.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.