Worked example
Example: 5 000 cd, 6 m high, 4 m to the side. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Luminous intensity in the direction of the point, I(θ) (candela) | 5,000.0 - |
| Mounting height above the surface | 6.0000 m |
| Horizontal distance from the point below the lamp | 4.0000 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Distance from the lamp to the point | 7.2111 m |
| Angle of incidence | 33.690 ° |
| Illuminance on the horizontal surface (lux) | 80.005 |
| Illuminance on a surface facing the lamp (lux) | 96.154 |
Open this example in the calculator and change any input.
Formula
\(E_h = \frac{I \cos\theta}{d^2} = \frac{I\, h}{(h^2 + x^2)^{3/2}}, \quad E_n = \frac{I}{d^2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I\) | Luminous intensity in the direction of the point, I(θ) (candela) | - |
| \(h\) | Mounting height above the surface | m |
| \(x\) | Horizontal distance from the point below the lamp | m |
| \(d\) | Distance from the lamp to the point | m |
| \(\theta\) | Angle of incidence | rad |
| \(E_h\) | Illuminance on the horizontal surface (lux) | - |
| \(E_n\) | Illuminance on a surface facing the lamp (lux) | - |
Method and standards
Point-source photometry.
Where it is used
- Flood, street and task lighting checks.
- Electrical examinations.
Common mistakes
- Using lumens for candela.
- Forgetting the cosine.
Assumptions and limits
- Point source, no reflections.
- I is the intensity in the direction of the point, I(θ), from the luminaire's polar curve; the nadir (0°) value applies only to the point directly below.
References
- Inverse-square law and Lambert's cosine law
Questions and answers
What lux does 5000 cd give 4 m to the side from 6 m high?
80.0 lux on the floor; 139 lux directly below.
Why does it fall so fast to the side?
Distance grows and the light strikes at a slant: the cos³ law.
When is the lumen method better?
For average illuminance of a room with many fittings and reflections.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.