Worked example
Example: Illustrative LED office. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated life to 70 % lumens | 50,000 h |
| Operating hours to maintenance | 25,000 h |
| Lamp survival factor | 100.00 % |
| Luminaire maintenance factor | 90.000 % |
| Room surface maintenance factor | 95.000 % |
| Maintained illuminance required | 500.00 lx |
Applying the formula below gives:
| Result | Value |
|---|---|
| Lamp lumen maintenance factor | 83.666 % |
| Maintenance factor | 71.534 % |
| Initial illuminance to design for | 698.96 lx |
| Over-lighting when new | 39.793 % |
Open this example in the calculator and change any input.
Formula
\(MF = LLMF\cdot LSF\cdot LMF\cdot RSMF, \quad LLMF = 0.7^{t/L_{70}}, \quad E_i = \frac{E_m}{MF}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L_{70}\) | Rated life to 70 % lumens | s |
| \(t\) | Operating hours to maintenance | s |
| \(LSF\) | Lamp survival factor | - |
| \(LMF\) | Luminaire maintenance factor | - |
| \(RSMF\) | Room surface maintenance factor | - |
| \(E_m\) | Maintained illuminance required | lx |
| \(LLMF\) | Lamp lumen maintenance factor | - |
| \(MF\) | Maintenance factor | - |
| \(E_i\) | Initial illuminance to design for | lx |
| \(1/MF - 1\) | Over-lighting when new | - |
Method and standards
Maintenance factor.
Where it is used
- Lighting design by the lumen method.
- Maintenance planning.
Common mistakes
- Using MF = 1 for LED.
- Ignoring room surface dirt in industry.
Assumptions and limits
- Exponential lumen depreciation.
References
- Maintenance factor components
- Lighting Handbook practice (lumen method, maintenance factor components)
Questions and answers
What maintenance factor is typical?
About 0.7–0.85 for clean offices with LED; 0.5–0.65 in dirty industrial areas.
Why design for initial illuminance above the target?
Lamps dim and fittings get dirty; the installation must still give the maintained value at the end of the maintenance period.
What do the defaults represent?
An illustrative LED installation with L70 of 50,000 h, maintenance at 25,000 h, LMF 0.9, RSMF 0.95, for 500 lx maintained.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.