Worked example
Example: Illustrative two LED panels. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Background luminance | 40.000 - |
| Luminance of luminaire 1 (cd/m²) | 6,000.0 - |
| Solid angle of luminaire 1 (sr) | 0.004000 - |
| Guth position index 1 | 2.5000 - |
| Luminance of luminaire 2 | 6,000.0 - |
| Solid angle 2 | 0.003000 - |
| Guth index 2 | 4.0000 - |
| Luminance of luminaire 3 | 0 - |
| Solid angle 3 | 0 - |
| Guth index 3 | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Glare sum ΣL²ω/p² | 29,790 |
| Unified glare rating | 18.160 |
Open this example in the calculator and change any input.
Formula
\(UGR = 8\log_{10}\left(\frac{0.25}{L_b}\sum\frac{L^2\omega}{p^2}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L_b\) | Background luminance | - |
| \(L_1\) | Luminance of luminaire 1 (cd/m²) | - |
| \(\omega_1\) | Solid angle of luminaire 1 (sr) | - |
| \(p_1\) | Guth position index 1 | - |
| \(L_2\) | Luminance of luminaire 2 | - |
| \(\omega_2\) | Solid angle 2 | - |
| \(p_2\) | Guth index 2 | - |
| \(L_3\) | Luminance of luminaire 3 | - |
| \(\omega_3\) | Solid angle 3 | - |
| \(p_3\) | Guth index 3 | - |
| \(\Sigma\) | Glare sum ΣL²ω/p² | - |
| \(UGR\) | Unified glare rating | - |
Method and standards
Glare rating.
Where it is used
- Office and control room lighting design.
- Comparing luminaire options.
Common mistakes
- Using luminaire intensity instead of luminance.
- Taking the Guth index for the wrong viewing direction.
Assumptions and limits
- Valid for luminaires of solid angle about 0.0003–0.1 sr.
References
- UGR formula
- CIE 117
- Discomfort Glare in Interior Lighting (UGR formula)
Questions and answers
What UGR is acceptable in an office?
19 or below for screen work and reading; workshops often accept 22–25.
Why does background luminance matter?
A brighter background reduces the contrast of the luminaires, lowering glare.
What do the defaults represent?
Two illustrative LED panels at 6,000 cd/m² seen at 0.004 and 0.003 sr with Guth indices 2.5 and 4 against a 40 cd/m² background.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Boyce, Human Factors in Lighting, 3rd ed. (CRC, 2014)