Lighting Energy with Daylight Dimming and Occupancy Control

Annual lighting energy with and without daylight-linked dimming and occupancy control, standby power of controls, savings and energy per square metre.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 12 kW office floorWarehouse, occupancy onlyPerimeter classroom

Accepted: 0.01 to 10,000 kW
Accepted: 1 to 8,750 h
Accepted: 0 to 100 %
Accepted: 0 to 100 %
Accepted: 10 to 100 %
Accepted: 0 to 100,000 W
Accepted: 1 to 1,000,000 m²

Results

E_c = P_it_yF_o(1 − F_ds_d) + P_s·8760 h. Daylight savings depend on window size, depth of the zone and sensor placement; occupancy savings on how often spaces are empty. Control standby power runs all year. The last output is in kWh/m² per year.

Annual energy without controls4,000.0kWh
Annual energy with controls1,671.6kWh
Saving58.210%
Annual energy per square metre (kWh/m²)8.3580

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 12 kW office floor. The inputs, in the units selected above:

InputValue
Installed lighting power12.000 kW
Annual operating hours3,000.0 h
Share of hours with useful daylight50.000 %
Average dimming saving in those hours60.000 %
Occupancy factor (fraction of time lights needed)85.000 %
Standby power of controls60.000 W
Floor area1,000.0 m²

Applying the formula below gives:

ResultValue
Annual energy without controls36,000 kWh
Annual energy with controls21,946 kWh
Saving39.040 %
Annual energy per square metre (kWh/m²)21.946

Open this example in the calculator and change any input.

Formula

\(E_c = P_it_yF_o(1 - F_ds_d) + P_s\cdot 8760\,\text{h}\)

Variables

Symbol Meaning SI unit
\(P_i\) Installed lighting power W
\(t_y\) Annual operating hours s
\(F_d\) Share of hours with useful daylight -
\(s_d\) Average dimming saving in those hours -
\(F_o\) Occupancy factor (fraction of time lights needed) -
\(P_s\) Standby power of controls W
\(A\) Floor area m²
\(E_0\) Annual energy without controls J
\(E_c\) Annual energy with controls J
\(\Delta E/E_0\) Saving -
\(E_c/A\) Annual energy per square metre (kWh/m²) -

Method and standards

Lighting energy.

Where it is used

  • Lighting controls business cases.
  • Building energy targets.

Common mistakes

  • Applying daylight savings to the whole floor.
  • Ignoring control standby losses.

Assumptions and limits

  • Average factors over the year.

References

  • Lighting energy with control factors

Questions and answers

How much does daylight dimming save?

Typically 20–60 % in perimeter zones near windows, little in deep-plan interiors.

Why include standby power?

Sensors and dimmable drivers draw power all year; in small, efficient installations it can eat into savings.

What do the defaults represent?

An illustrative 12 kW installation on 1,000 m² running 3,000 h a year, half of it with useful daylight saving 60 %, occupancy factor 0.85 and 60 W standby.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Simpson, Lighting Control: Technology and Applications (Focal Press, 2003)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.