Worked example
Example: Illustrative 12 kW office floor. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Installed lighting power | 12.000 kW |
| Annual operating hours | 3,000.0 h |
| Share of hours with useful daylight | 50.000 % |
| Average dimming saving in those hours | 60.000 % |
| Occupancy factor (fraction of time lights needed) | 85.000 % |
| Standby power of controls | 60.000 W |
| Floor area | 1,000.0 m² |
Applying the formula below gives:
| Result | Value |
|---|---|
| Annual energy without controls | 36,000 kWh |
| Annual energy with controls | 21,946 kWh |
| Saving | 39.040 % |
| Annual energy per square metre (kWh/m²) | 21.946 |
Open this example in the calculator and change any input.
Formula
\(E_c = P_it_yF_o(1 - F_ds_d) + P_s\cdot 8760\,\text{h}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_i\) | Installed lighting power | W |
| \(t_y\) | Annual operating hours | s |
| \(F_d\) | Share of hours with useful daylight | - |
| \(s_d\) | Average dimming saving in those hours | - |
| \(F_o\) | Occupancy factor (fraction of time lights needed) | - |
| \(P_s\) | Standby power of controls | W |
| \(A\) | Floor area | m² |
| \(E_0\) | Annual energy without controls | J |
| \(E_c\) | Annual energy with controls | J |
| \(\Delta E/E_0\) | Saving | - |
| \(E_c/A\) | Annual energy per square metre (kWh/m²) | - |
Method and standards
Lighting energy.
Where it is used
- Lighting controls business cases.
- Building energy targets.
Common mistakes
- Applying daylight savings to the whole floor.
- Ignoring control standby losses.
Assumptions and limits
- Average factors over the year.
References
- Lighting energy with control factors
Questions and answers
How much does daylight dimming save?
Typically 20–60 % in perimeter zones near windows, little in deep-plan interiors.
Why include standby power?
Sensors and dimmable drivers draw power all year; in small, efficient installations it can eat into savings.
What do the defaults represent?
An illustrative 12 kW installation on 1,000 m² running 3,000 h a year, half of it with useful daylight saving 60 %, occupancy factor 0.85 and 60 W standby.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.