Worked example
Example: Illustrative 50 kcd from 12 m mast at 20 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Luminous intensity toward the point (cd) | 50,000 - |
| Mounting height above the point | 12.000 m |
| Horizontal distance from the mast | 20.000 m |
| Plane tilt from horizontal, facing the mast | 30.000 ° |
Applying the formula below gives:
| Result | Value |
|---|---|
| Distance to the luminaire | 23.324 m |
| Horizontal illuminance | 47.288 lx |
| Vertical illuminance facing the mast | 78.814 lx |
| Illuminance on the inclined plane | 80.360 lx |
Open this example in the calculator and change any input.
Formula
\(E_h = \frac{Ih}{d^3}, \quad E_v = \frac{Ix}{d^3}, \quad E_\beta = \frac{I(h\cos\beta + x\sin\beta)}{d^3}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I\) | Luminous intensity toward the point (cd) | - |
| \(h\) | Mounting height above the point | m |
| \(x\) | Horizontal distance from the mast | m |
| \(\beta\) | Plane tilt from horizontal, facing the mast | rad |
| \(d\) | Distance to the luminaire | m |
| \(E_h\) | Horizontal illuminance | lx |
| \(E_v\) | Vertical illuminance facing the mast | lx |
| \(E_\beta\) | Illuminance on the inclined plane | lx |
Method and standards
Point illuminance.
Where it is used
- Yard, coal stockpile and sports floodlighting.
- Security and CCTV lighting checks.
Common mistakes
- Using the peak intensity instead of the intensity toward the point.
- Forgetting the maintenance factor.
Assumptions and limits
- Point source; no obstruction or reflections.
References
- Inverse-square and cosine laws
Questions and answers
Why does vertical illuminance matter?
Faces, signs, stacks of goods and cameras need light on vertical surfaces, not just the ground.
Where does intensity come from?
From the luminaire's photometric file (IES or LDT) at the angle from its aiming direction to the point.
What do the defaults represent?
An illustrative 50,000 cd floodlight 12 m up, 20 m horizontally from the point, and a plane tilted 30° towards the mast.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Boyce, Human Factors in Lighting, 3rd ed. (CRC, 2014)