FireCADCalc

Floodlight Illuminance on Horizontal, Vertical and Inclined Planes

Illuminance at a point from a floodlight of known intensity, on horizontal, vertical (facing the mast) and inclined planes, by the inverse-square and cosine laws.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 50 kcd from 12 m mast at 20 mClose to mast, vertical planeStockpile face 45 deg at 40 m

Accepted: 1 to 10,000,000
Accepted: 0.5 to 100 m
Accepted: 0 to 300 m
Accepted: 0 to 90 °

Results

E = I·cosθ/d², θ between the light ray and the surface normal: horizontal cosθ = h/d, vertical facing the mast x/d, inclined (h·cosβ + x·sinβ)/d. Read I from the floodlight's polar data at the aiming angle; add contributions of all floodlights and apply a maintenance factor.

Distance to the luminaire9.4340m
Horizontal illuminance190.56lx
Vertical illuminance facing the mast119.10lx
Illuminance on the inclined plane119.10lx

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 50 kcd from 12 m mast at 20 m. The inputs, in the units selected above:

InputValue
Luminous intensity toward the point (cd)50,000 -
Mounting height above the point12.000 m
Horizontal distance from the mast20.000 m
Plane tilt from horizontal, facing the mast30.000 °

Applying the formula below gives:

ResultValue
Distance to the luminaire23.324 m
Horizontal illuminance47.288 lx
Vertical illuminance facing the mast78.814 lx
Illuminance on the inclined plane80.360 lx

Open this example in the calculator and change any input.

Formula

\(E_h = \frac{Ih}{d^3}, \quad E_v = \frac{Ix}{d^3}, \quad E_\beta = \frac{I(h\cos\beta + x\sin\beta)}{d^3}\)

Variables

Symbol Meaning SI unit
\(I\) Luminous intensity toward the point (cd) -
\(h\) Mounting height above the point m
\(x\) Horizontal distance from the mast m
\(\beta\) Plane tilt from horizontal, facing the mast rad
\(d\) Distance to the luminaire m
\(E_h\) Horizontal illuminance lx
\(E_v\) Vertical illuminance facing the mast lx
\(E_\beta\) Illuminance on the inclined plane lx

Method and standards

Point illuminance.

Where it is used

  • Yard, coal stockpile and sports floodlighting.
  • Security and CCTV lighting checks.

Common mistakes

  • Using the peak intensity instead of the intensity toward the point.
  • Forgetting the maintenance factor.

Assumptions and limits

  • Point source; no obstruction or reflections.

References

  • Inverse-square and cosine laws

Questions and answers

Why does vertical illuminance matter?

Faces, signs, stacks of goods and cameras need light on vertical surfaces, not just the ground.

Where does intensity come from?

From the luminaire's photometric file (IES or LDT) at the angle from its aiming direction to the point.

What do the defaults represent?

An illustrative 50,000 cd floodlight 12 m up, 20 m horizontally from the point, and a plane tilted 30° towards the mast.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Boyce, Human Factors in Lighting, 3rd ed. (CRC, 2014)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.