Skin Depth and AC Resistance of a Round Conductor

Skin depth at a frequency and the AC-to-DC resistance ratio of a round conductor from its diameter, resistivity and relative permeability.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 25 mm copper at 50 HzSteel 20 mm at 50 Hz25 mm copper at 100 kHz

Results

Isolated straight round conductor; proximity effect from nearby conductors is extra. Copper at 50 Hz has δ ≈ 9.3 mm, so skin effect matters for large single conductors and busbars.

Skin depth1.2328mm
Diameter-to-skin-depth ratio16.223
AC-to-DC resistance ratio4.3172

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 25 mm copper at 50 Hz. The inputs, in the units selected above:

InputValue
Frequency50.000 Hz
Conductor diameter25.000 mm
Resistivity1.7240e-08 Ω·m
Relative permeability1.0000 -

Applying the formula below gives:

ResultValue
Skin depth9.3455 mm
Diameter-to-skin-depth ratio2.6751
AC-to-DC resistance ratio1.0633

Open this example in the calculator and change any input.

Formula

\(\delta = \sqrt{\frac{\rho}{\pi f\mu_0\mu_r}}, \quad \frac{R_{ac}}{R_{dc}} = \mathrm{Re}\left[\frac{kr}{2}\frac{J_0(kr)}{J_1(kr)}\right],\ k = \frac{1 - j}{\delta}; \quad \approx \frac x4 + \frac14 + \frac{3}{16x}\ (x = d/\delta > 20)\)

Variables

Symbol Meaning SI unit
\(f\) Frequency 1/s
\(d\) Conductor diameter m
\(\rho\) Resistivity Ω·m
\(\mu_r\) Relative permeability -
\(\delta\) Skin depth m
\(d/\delta\) Diameter-to-skin-depth ratio -
\(R_{ac}/R_{dc}\) AC-to-DC resistance ratio -
\(\mu_0\) Magnetic constant, 1.256 637 062 12 × 10⁻⁶ H/m
\(k\) Complex propagation constant (1 − j)/δ 1/m
\(r\) Conductor radius d/2 m
\(J_0, J_1\) Bessel functions of the first kind -
\(x\) d/δ -

Method and standards

Exact Bessel solution (power series), asymptotic form for very large d/δ.

Where it is used

  • Busbar and large cable design.
  • High-frequency induction heating.

Common mistakes

  • Ignoring proximity effect in bundles.
  • Using copper resistivity at 20 °C for hot conductors.

Assumptions and limits

  • Isolated round conductor.
  • Above d/δ = 20 the three-term asymptotic form r/(2δ) + 1/4 + 3δ/(32r) (with r = d/2) is used; it agrees with the series solution to about 0.002 % at the switch, and closer above it.

References

  • Skin depth δ = √(ρ/(πfμ)); exact Bessel-function solution for a round wire
  • Z/R_dc = (kr/2)J₀(kr)/J₁(kr) with k = (1 − j)/δ (Ramo, Whinnery and Van Duzer, Fields and Waves in Communication Electronics, 3rd ed. (Wiley, 1994))

Questions and answers

What is skin depth?

The depth at which current density falls to 37 % of its surface value; current crowds into a layer about this thick.

When does it matter at 50 Hz?

For copper conductors above about 20 mm diameter and for steel (high μ), where δ is only about 1 mm.

What do the defaults represent?

A 25 mm copper conductor at 50 Hz.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.