Cable Short-Circuit Withstand (Adiabatic Equation)

Short-circuit current a copper or aluminium conductor withstands for a time by the adiabatic equation I²t = k²S², with k from the temperatures, and the size needed.

Thermal power plantProcess steam and utilities

Inputs

Examples: 95 mm² copper XLPE, 90 to 250 °C, 1 s; 20 kA185 mm² aluminium XLPE, 90 to 250 °C, 0.5 s; 25 kA16 mm² copper PVC, 70 to 160 °C, 0.2 s; 6 kA

From your cable's insulation data (cable standard or maker).

Results

Adiabatic: no heat leaves the conductor during the fault, which is safe for faults up to about 5 s. Screens, armour and joints have their own limits.

Factor k (A·s^½/mm²)114.83
Current the conductor withstands for the time4.1085kA
Smallest cross-section for the fault current23.366mm²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 95 mm² copper XLPE, 90 to 250 °C, 1 s; 20 kA. The inputs, in the units selected above:

InputValue
ConductorCopper
Conductor cross-section95.000 mm²
Duration of the fault1.0000 s
Conductor temperature before the fault90.000 °C
Highest temperature allowed at the end of the fault250.00 °C
Fault current, RMS symmetrical (to find the size needed)20.000 kA

Applying the formula below gives:

ResultValue
Factor k (A·s^½/mm²)142.87
Current the conductor withstands for the time13.573 kA
Smallest cross-section for the fault current139.98 mm²

Open this example in the calculator and change any input.

Formula

\(k = \sqrt{\frac{Q_c (\beta + 20)}{\rho_{20}} \ln\frac{\beta + \theta_f}{\beta + \theta_i}}, \quad I_{max} = \frac{k\, S}{\sqrt t}, \quad S_{min} = \frac{I_k \sqrt t}{k}\)

Variables

Symbol Meaning SI unit
\(\text{metal}\) Conductor -
\(S\) Conductor cross-section m²
\(t\) Duration of the fault s
\(\theta_i\) Conductor temperature before the fault K
\(\theta_f\) Highest temperature allowed at the end of the fault K
\(I_k\) Fault current, RMS symmetrical (to find the size needed) A
\(k\) Factor k (A·s^½/mm²) -
\(I_{max}\) Current the conductor withstands for the time A
\(S_{min}\) Smallest cross-section for the fault current m²

Method and standards

All the fault energy heats the conductor; resistance rises with temperature.

Where it is used

  • Checking cable size against the protection clearing time.
  • Earth and protective conductors.

Common mistakes

  • Using the breaker rating instead of the clearing time.
  • Wrong starting temperature.

Assumptions and limits

  • Adiabatic; conductor only.
  • I_k is the RMS symmetrical current; the DC component is neglected. For faults shorter than about 0.1 s the asymmetry matters: use the protective device's let-through I²t instead.

References

  • IEC 60949:1988 (adiabatic short-circuit calculation; material constants of Table I)

Questions and answers

What can 95 mm² copper carry for 1 s from 90 °C to 250 °C?

k = 143, so about 13.6 kA.

What size for 20 kA for 1 s?

140 mm² at least: choose the next standard size.

Where do the temperatures come from?

The insulation's operating and short-circuit limits in the cable standard or maker's data.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.