FireCADCalc

Battery Heat Generation and Temperature Rise

Irreversible (Joule) and reversible (entropic) heat of a battery cell and pack at a current, and the adiabatic temperature rise rate from the pack mass.

Thermal power plant

Inputs

Examples: Illustrative 96 cells, 50 AFast charge 200 ALow rate 5 A: entropic heat matters

Accepted: -1,000 to 1,000 A
Accepted: 1E-5 to 1 Ω
Accepted: -40 to 80 °C
Accepted: -0.002 to 0.002
Accepted: 1 to 10,000
Accepted: 0.01 to 100,000 kg
Accepted: 0.3 to 2 kJ/(kg·K)

Results

Bernardi form: Q = I²R − IT(dU/dT) with I positive on discharge. The reversible term changes sign between charge and discharge and matters at low C-rates; Joule heat dominates at high rates. The temperature rise rate assumes no cooling.

Joule heat per cell0.060000kW
Reversible heat per cell-0.006163kW
Total heat per cell0.053837kW
Pack heat5.8144kW
Adiabatic temperature rise rate0.012306K/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 96 cells, 50 A. The inputs, in the units selected above:

InputValue
Cell current (positive discharge)50.000 A
Cell internal resistance0.002000 Ω
Cell temperature25.000 °C
Entropic coefficient of open-circuit voltage (V/K)-1.0000e-04 -
Cells in the pack96.000 -
Pack mass300.00 kg
Pack specific heat1.0000 kJ/(kg·K)

Applying the formula below gives:

ResultValue
Joule heat per cell0.005000 kW
Reversible heat per cell0.001491 kW
Total heat per cell0.006491 kW
Pack heat0.62311 kW
Adiabatic temperature rise rate0.002077 K/s

Open this example in the calculator and change any input.

Formula

\(\dot Q = I^2R - IT\frac{dU}{dT}, \quad \frac{dT}{dt} = \frac{n\dot Q}{mc_p}\)

Variables

Symbol Meaning SI unit
\(I\) Cell current (positive discharge) A
\(R\) Cell internal resistance Ω
\(T\) Cell temperature K
\(dU/dT\) Entropic coefficient of open-circuit voltage (V/K) -
\(n\) Cells in the pack -
\(m\) Pack mass kg
\(c_p\) Pack specific heat J/(kg·K)
\(\dot Q_{irr}\) Joule heat per cell W
\(\dot Q_{rev}\) Reversible heat per cell W
\(\dot Q\) Total heat per cell W
\(\dot Q_{pack}\) Pack heat W
\(dT/dt\) Adiabatic temperature rise rate K/s

Method and standards

Battery heat.

Where it is used

  • Thermal management design for EVs and stationary packs.
  • Cooling system sizing.

Common mistakes

  • Ignoring internal resistance growth at low temperature.
  • Assuming the reversible heat is always positive.

Assumptions and limits

  • Uniform temperature; constant properties.

References

  • Bernardi battery heat generation

Questions and answers

Why does fast charging heat batteries?

Joule heat grows with the square of current; doubling the charging rate quadruples it.

What is reversible heat?

Heat from the entropy change of the cell reaction; it can cool or heat the cell depending on direction and chemistry.

What do the defaults represent?

An illustrative pack of 96 cells of 2 mΩ at 50 A and 25 °C with dU/dT −0.1 mV/K, 300 kg and 1,000 J/(kg·K).

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.